Page 200 - Boiler_Operators_Handbook,_Second_Edition
P. 200

Refrigeration & AC                                                                                  185

                                                                    Blockage of the pan or drain piping by condensate con-
                                                                    taminated with dust or other debris is a common prob-
                                                                    lem  with  air  conditioning  equipment.  Elimination  of
                                                                    the condensate can also be a concern; in hospitals, simi-
                                                                    lar medical facilities, and production plants the drain is
                                                                    piped to a sanitary sewer for obvious reasons. In some
                                                                    cases the drain piping can’t slope down to discharge
                                                                    into the sewer or a suitable discharge point so small
                                                                    sumps and pumps are provided to lift the condensate
                                                                    into a suitable discharge area. The drains should be ar-
                                                                    ranged in a manner that prevents sewer gases or other
                                                                    contamination from leaking into the air conditioning
                                                                    system and the normal solution for that is a ‘P’ trap
                                                                    like you find under a lavatory sink. A good remedy for
                                                                    those plugging up is to give them a fresh water rinse
                                                                    once a year. Regardless they should be checked quar-
                                                                    terly to ensure water isn’t flooding the drain pan.
                Figure 5-43. Cooling Coil Face and bypass dampers
               tures to match the cooling load. Combined with reheat  Inspection and Access Doors
               coils the face and bypass dampers also permit control     Checking the drain pan would include checking
               of the moisture content of the supply air as well as the  the condition of the cooling coil, inlet and outlet, to
               temperature.                                         detect any undesirable accumulations on the coil or in
                    Note that the damper blades do not operate in  the drain pan. In order to check them there has to be a
               parallel. These opposed blade dampers provide a more  means of looking into, and in large units, entering the
               linear  position  to  airflow  relationship  for  better  con-  space between the filters and the cooling coil. Inspec-
               trol. The face and bypass dampers operate opposite  tion and access doors are normally provided for this
               each other, one closes as the other opens and the design  purpose and, hopefully, access to them isn’t blocked by
               provides for a pressure drop through the open bypass  the piping and wiring on the outside of the unit. The
               damper that equals that of the cooling coil and open  covers or doors for these openings range from a thin
               face dampers so the air flow quantity isn’t altered by  piece of sheet metal to a rugged, insulated door with
               the operation of these dampers.                      latching handles and hinges. They should not be left
                    In constant air flow systems two means are avail-  open, half hanging, or loosely mounted because the air
               able for controlling the equipment outlet temperature  pressure  in  the  apparatus  is  negative  after  the  filters
               when cooling, one is to cool all the air then to reheat  and air leaking in bypasses the filters.
               the air with heating coils (not necessarily in the air     If, as in so many cases, the openings are simply
               handler) to maintain conditioned air temperature. To  covered with a piece of sheet metal then it’s good prac-
               control the apparatus outlet temperature chilled wa-  tice to replace the gasket that should be glued to the
               ter can be regulated by throttling the flow of water or  cover when it’s accidentally damaged and to replace
               bypassing some of it. Refrigeration temperatures can  any screws that get lost. When replacing the cover
               be adjusted with compressor controls and face and by-  care should be taken to simply draw up the cover un-
               pass dampers allow some of the air to pass through the  til the gasket is seated then stop turning the screw. If
               apparatus without contacting the cooling coil and mix  you don’t the metal cover will bow leaving gaps be-
               with the air passing through the cooling coil.       tween the screw holes that allow unfiltered air into the
                    The cooling coil not only removes heat, it con-  AHU. Whenever the cover screws simply spin, because
               denses moisture in the air to produce the equipment  the sheet metal of the AHU is stripped, look for larg-
               outlet conditions. Velocity of the air over the cooling  er screws that have plastic knobs on them to replace
               coil is typically limited to 500 feet per minute so the  those old screws. The larger screws will engage in the
               droplets of condensed moisture drizzle down the fins  stripped holes and the plastic knobs make it possible to
               to the drain pan instead of being carried off with the  remove and replace them without tools while prevent-
               supply air. The condensed water dripping off the coils  ing  application  of  too  much  torque  that  stripped  the
               is collected in a drain pan connected to drain piping.  screw holes in the first place. Oh, by the way, get new
   195   196   197   198   199   200   201   202   203   204   205