296                                                                               Boiler Operator’s Handbook


                                                                    water flashes to form more steam resulting in an explo-
                                                                    sion. Hot water heaters commonly rocket their way up
                                                                    through as many floors as are above them and have flat-
                                                                    tened many houses.
                                                                        The temperature element of a PTV is a small cylin-
                                                                    drical tube that extends from the inlet of the valve. The
                                                                    valve must be installed so that element will be immersed
                                                                    in the hot water. Mounting the valve on connecting pip-
                                                                    ing will not work because the element isn’t exposed to
                                                                    the heat. Since the element must be in contact with the
                                                                    heated water PTVs can be installed horizontally and,
                                                                    when labeled for it, even upside down. Don’t make the
                                                                    mistake of one contractor in Oklahoma who decided the
                                                                    PTVs were installed wrong (the stems weren’t vertical)
                                                                    so he went out to the local hardware and got some street
                                                                    ells (piping elbows with male thread at one end and a
                                                                    female thread at the other) to add and turn the PTVs.
                                                                    The worker assigned the job of changing the valves had
                                                                    a problem with the little pencil like things hanging out
                                                                    of the bottom of the valves (they prevented installation
                                                                    on the street ell) so he broke them off. Lacking the ther-
                                                                    mal element the PTVs didn’t work when other controls
                                                                    failed and the heaters exploded. Six children and one
                                                                    adult were killed and forty-two others were injured. It
                                                                    was an 80 gallon water heater.
                Figure 10-31. Safety valve seat exposed to pressure     Boilers larger than 100 horsepower must have two
                                                                    safety valves, that’s a code requirement. Also, boilers
               About the only time a PTV will operate on pressure is  with superheaters have to have a safety valve at the
               when the water is trapped by a check valve or backflow  outlet of the superheater which is set lower than the
               preventer (see service water heating) and the pressure is  safety valves on the steam drum. It’s essential that the
               increased by the water expanding as it is heated.    superheater safety valve opens first to maintain a flow of
                    If the controls fail to shut down the burner or elec-  steam through the superheater to prevent it overheating.
               tric element or steam supplying a service water heater     In addition to monthly and annual testing of safety
               the pressure usually doesn’t increase because the pres-  valves (see normal operating procedures) you may be
               sure is dependent on the water supply. Expansion of the  required to send the safety valves out to be replaced or
               heated water simply pushes the cold water back down  rebuilt. That’s normally a requirement of the insurance
               the line out of the heater. Herein lies the problem, when  company that doesn’t want their inspectors to spend
               the heat continues the water eventually gets so hot that  time observing the pop testing of safety valves. It’s less
               it starts to turn to steam. The steam takes up a lot more  expensive  to  simply  replace  a  small  valve  but  valve
               room than the water and pushes the hot water back the  prices increase with size and set pressure to where you
               cold water line until the heating element or the bottom  would want to have them rebuilt at a much lower cost.
               of the heater is exposed to steam instead of water. Now,  A contractor that rebuilds safety valves should have
               the steam picks up some heat as it is superheated but it  ASME or National Board authorization to do that work.
               can’t provide all the cooling that evaporating water does     You’ll also want to replace a valve or send the
               so the temperature of the heating element or the bottom  valve out for rebuilding if it starts weeping or leak-
               of the heater rises until they get so hot that they fail.  ing. The steam condensing on the spring and stem will
                    Luckily for those of us that have electric hot water  accelerate rusting in the topworks of the safety valve
               heaters the element shorts out or burns open to stop  which can prevent it operating. Continuously operating
               adding heat. If you have a piece of fired equipment  a boiler with a leaking safety valve is hazardous.
               the outcome is not so pleasant, the weakened surface     When I encounter leaking safety valves I always
               of the heater ruptures. The steam expands and the hot  check the vent piping immediately. In my experience it’s