Page 322 - Boiler_Operators_Handbook,_Second_Edition
P. 322

Plants and Equipment                                                                                307


               HEAT TRAPS                                           loads and you have an opportunity for generating steam
                                                                    in the economizer. Generating steam in the economizer
                    There’s a general use of the term heat trap to refer
                                                                    will promote scaling of the water sides of the economiz-
               to anything that is added to a boiler to absorb heat re-
                                                                    er and potential damage from water hammer as flows
               maining in the flue gas. They normally return that heat
                                                                    change.
               directly to the boiler. Conventional heat traps are econo-
                                                                        When the feedwater control valve is between the
               mizers and air preheaters. Condensing heat exchangers
                                                                    economizer and boiler the probability of steaming is re-
               can be used as either an economizer or air preheater but
                                                                    duced because the economizer operates at a higher pres-
               are commonly used to heat water for other purposes.
                                                                    sure but the control valve will take a beating as some
               Economizers                                          of the water flashes to steam as it goes through it. The
                    An economizer traps heat by transferring energy  feedwater piping in the boiler drum will also be exposed
               from the flue gas to the boiler feedwater so that heat  to water hammering and erosion from the flashing
               doesn’t leave the boiler. Economizers are only found in  steam. There are such things as steaming economizers
               high pressure steam plants. They don’t work on most  but they’re designed to do it; a normal economizer is not
               low pressure or any of the HTHW plants, and some  designed to generate steam at any load.
               high pressure plants can’t benefit from the addition of     If you have wide variations in load the economizer
               an economizer. An economizer can work in a low pres-  of each boiler should be fitted with a return line to dump
               sure steam plant that has no condensate returns because  some of the feedwater back to the deaerator. By adjust-
               the feedwater temperature would be much lower than  ing a globe valve in that line you can control the outlet
               steam temperature. If you have a low pressure plant  temperature at low loads.
               with little condensate return such that the feedwater     I always provide bypass and isolating valves be-
               temperature (before heating in a feed tank) would be  cause there’s no reason to limit boiler operation to include
               around 100°F lower than the steam temperature then  the economizer. If the economizer has problems draining
               an economizer could be used to trap some of the energy  it and bypassing it will not damage it because the flue gas
               lost up the stack but we would probably call it a CHX for  temperatures will not be hot enough to hurt it.
               reasons that will become evident.                        An economizer is typically constructed of tubes
                    When the boiler feedwater is colder than the steam  just like boiler tubes with those tubes rolled or welded
               and water in the boiler, it can extract more heat from  into headers. The tubes can be bare but are usually fit-
               the flue gas. Fluids colder than what’s in the boiler can  ted with fins to increase the heat transfer surface (Figure
               also be used in an economizer to recover the heat. An  10-40) There are two standard arrangements of construc-
               economizer on a high pressure boiler plant makes it as  tion, square, where the tubes are straight and connected
               efficient as low pressure boilers because the feedwater  to each other by bends, and circular where the tubes
               supplied to the economizer inlet is about the same tem-  form a coil between the two headers. The circular econo-
               perature as steam and water in a low pressure boiler. It’s
               important to be certain the feedwater flows through the
               economizer in the opposite direction of the flue gas so it
               sees hotter flue gas as it heats up and the coldest water
               is exposed to the gas just before it leaves the economizer.
               Economizers can heat feedwater to a higher temperature
               than the flue gas leaving the economizer because of the
               counterflow arrangement.
                    At low loads there are some concerns with econo-
               mizer operation which can restrict the turndown capa-
               bility of the boiler. When the economizer is mounted in
               the stack or on top of the boiler the water has to flow
               down through the economizer. The natural tendency of
               heated water is to rise up through colder water because
               it’s lighter (the thermal-siphoning effect) so water flow
               through the economizer can become unstable at low
               loads. Combine that with the fact that the heating sur-
               face doesn’t change so heat transfer improves at lower      Figure 10-40. Finned tube economizer
   317   318   319   320   321   322   323   324   325   326   327