308                                                                               Boiler Operator’s Handbook


               mizers are less expensive initially but almost impossible
               to repair.
                    Since economizers can be subjected to corrosive
               conditions more frequently than the boiler the materials
               of construction may be special to resist corrosion. Com-
               bustion Engineering developed cast iron muffs, cast
               pieces that look like finned tubes pressed over the steel
               tubes, which provided a corrosion resistant covering for
               excellent performance on coal and heavy fuel oil fired
               boilers because the iron conducted heat well in addition
               to resisting corrosion. Modern metallurgy has created
               materials that permit construction of economizers that
               can  withstand very  corrosive  conditions  permitting
               closer operation to the flue gas acid dewpoints without
               concern for serious damage.
                    In addition to corrosion economizers can have
               problems with soot accumulation, occasional plugging
               with unburned fuel, and unique situations (Figure 10-
               41) with waste fuels. The tube in the top of the picture  Figure 10-41. Plugged economizer, firing waste fuel
               is the soot blower, you can see the coated fins in the
               bottom of the picture. Soot and dirt manage to build  temperature to reduce potential for corrosion in the
               up between the fins of finned economizers to almost  economizer and reduces the required size of later stages
               completely block heat transfer. Even if there’s no rea-  of the turbine for overall cost savings.
               son to believe you will have problems of blockage an     The best economizer arrangement (and also the
               economizer should be supplied with a means to clean  most  expensive)  is  where  the  flue  gases  flow  down
               it or provisions to install them in the future. The com-  through the economizer. For counterflow the feedwater
               mon in-service method of cleaning is using soot blowers  flows up through and that prevents problems with strat-
               but they are ineffective when the deposits forms a hard  ification and thermal siphoning. A turning box under
               gelatinous mass so there should also be means to gain  the economizer can also serve as a drain pan for wash
               access to the economizer to clean it with water washing.  water used to clean the economizer. However, those
                    Some economizer applications (like the one in Fig-  installations introduce a hazard when the boiler is idle
               ure 10-41) require regular cleaning, a tough and dirty job  because any natural gas or other fuel vapors which are
               for the boiler operators. The savings in fuel makes the  lighter than air and get into the setting can accumulate
               effort worth it.                                     because the boiler and economizer arrangement forms a
                    Gas fired operations produce flue gas with very  trap to hold them. I prefer to install an access door in the
               low acid dewpoints so you can operate a deaerator sup-  top of the ductwork between the economizer and boiler
               plying economizers or low pressure boilers at lower  to vent it prior to entering the setting for inspection or
               feedwater temperatures when firing gas than when fir-  maintenance.
               ing oil or other fuels with higher carbon and sulfur con-     I hate to call an economizer a heat trap because
               tent. If gas is the primary fuel you can adjust (slowly)  it’s so much more than that. In addition to capturing
               deaerator pressures to raise the feedwater temperature  heat that would be lost it provides additional heating
               when firing fuels with a higher acid dewpoint and lower  surface for transferring the energy that’s in the fuel into
               it for firing gas.                                   the steam and water. Adding an economizer to an exist-
                    An alternative to that, found in plants with auxilia-  ing high pressure boiler installation can also increase
               ry turbines designed for low exhaust pressures is to use  the capacity of the plant because heat that was absorbed
               a steam heated feedwater heater between the deaerator  through the boiler surface to raise the feedwater tem-
               and economizers to raise the feedwater temperature to  perature is now used to generate more steam. I’ve seen
               the point that corrosion will not occur when firing high  capacities increased by as much as 8%. Of course the
               sulfur fuels. Power generating plants normally use feed-  fan has to be replaced to overcome the pressure drop
               water heaters to condense some of the turbine steam and  through the economizer or that added capacity is lost.
               raise the feedwater temperature. It raises the feedwater     Economizers require some attention when starting