Page 318 - Boiler_Operators_Handbook,_Second_Edition
P. 318

Plants and Equipment                                                                                303


               Pressure and Temperature Limit Switches              mounted on a siphon the switch can be tilted as pressure
                    A boiler that vaporizes a fluid should always have  builds in the boiler because the siphon tends to straight-
               a high pressure switch to stop the burner or isolate the  en just like the Bourdon tube in a pressure gauge. That
               source of heat in the event the pressure in the boiler  would alter the switch operating point. If you have a
               gets too high. If the boiler simply heats a fluid it should  mercury bulb switch mounted on a siphon make sure
               have a high temperature switch. In some instances fluid  the travel of the mercury switch is perpendicular to the
               heating boilers are served by a common expansion tank  siphon.
               which can be isolated from the boiler so a high pressure     Temperature limit switches are normally installed
               switch is also provided.                             with a thermal bulb penetrating the boiler and the
                    A hot water or fluid system boiler can also have a  switch assembly right on the end of the bulb. When
               low pressure switch to prevent operation when the sys-  they’re mounted separately to keep  the wiring and
               tem pressure is so low that vapor would form out in the  switch isolated from the high temperatures in the boiler
               system (at the high point) to block liquid flow and pos-  it’s common for the assembly to include a capillary be-
               sibly cause the equivalent of water hammer to damage  tween the bulb and the switch bellows or diaphragm so
               the piping or heat utilization equipment.            the fluid expands in the bulb as it’s heated and some of
                    All high limit switches require a manual reset. In  the fluid is pressed into the capillary which displaces
               some jurisdictions this is interpreted as a switch which  fluid in the capillary, pushing it into the bellows or dia-
               will not close, once it’s opened by a high pressure or  phragm chamber to expand it and actuate the switch.
               temperature, until the operating personnel push a but-     If the capillary is crimped by bending or by physi-
               ton located on the switch. I prefer systems that require  cal abuse then the flat ends of the bulb tend to bulge out,
               the operator reset it at the control panel or boiler front  making more room for the expanding fluid because the
               and will argue with anyone that insists they be put on  crimping of the capillary restricts the movement of the
               the switch. In most cases that switch is above the reach  fluid in the assembly. The bulging of the flat ends of the
               of a boiler operator and it’s seldom mounted where the  bulb can act like a spring, maintaining pressure on the
               operator can conveniently get at it to push that reset but-  fluid so it eventually bleeds through the small restric-
               ton. I always suggest the proponents of reset switches  tion and acts on the switch. After the boiler cools the
               picture themselves alone in the plant at two in the morn-  bulging is restored first and it may even reverse, caving
               ing trying to climb up to the switch to push the button.  in at the end as the liquid shrinks to produce a pressure
               Remember that first priority?                        differential that forces the fluid back through the small
                    In addition to the high limit switch a boiler can  restriction and the switch resets.
               have a pressure or temperature control switch which      The liquid slowly bleeding through the restric-
               provides for on / off control of the boiler. These switches  tion results in the switch operating after a delay. Any
               are all directly connected to ensure they sense the actual  significant delay in the response of a limit or operating
               pressure or temperature in the boiler. Location of tem-  temperature control is probably due to damage to the
               perature switches is important, see the discussion on  capillary and the only solution is to replace the switch.
               boiler construction. Pressure switches will not have any  If the restriction is due to a repeated situation (like a
               valves separating them from the boiler unless they’re  plant where the operator’s climbed to reach a valve and
               rising stem valves and are locked in the open position  repeatedly stepped on a capillary draped over a sup-
               when the boiler is operating normally; a provision on a  port) the capillary can be shut off entirely and the switch
               boiler whose continued operation is critical.        won’t work.
                    Pressure switch sensing piping can plug up just     Since the switches are normally mounted on the
               like the pressure gauge sensing lines although a pres-  boiler or the steam drum it’s not at all unusual for them
               sure switch is normally mounted close to the boiler  to be located where they don’t get regular attention. The
               connection (it doesn’t have to be seen all the time like a  heat that radiates from the boiler and leaks through the
               gauge). It’s always important that the pressure switch  casing or lagging creates swirling air currents around
               has a siphon or piping arrangement which traps and  the boiler and its trim. The air currents can be warm one
               holds some liquid in the switch and immediate connect-  minute and cold the next so the air around pressure and
               ing piping to protect the switch from the high tempera-  temperature switches promotes breathing of the switch
               ture of the vapor.                                   housing to suck dust into the housing. Dust settles in-
                    Another concern with pressure switches that use  side the housing and can eventually block its operation.
               mercury switches is the mounting of the switch. If  That’s assuming the cover is on the housing; I would
   313   314   315   316   317   318   319   320   321   322   323