Page 381 - Boiler_Operators_Handbook,_Second_Edition
P. 381

366                                                                               Boiler Operator’s Handbook


               rent, or a bunch of electrical charges in a tiny microchip  we’re trying to control (process variable) is sensed by
               that we relate to as ones and zeros. If they don’t know  the controller which compares that value to the setpoint
               any more than that we shouldn’t have any problem  then adjusts its output accordingly. The change in out-
               understanding them. Understanding controls isn’t that  put produces a change in the process variable and the
               difficult, our controls can be used in any application, not  controller compares that new value to the setpoint to
               just boiler plants. The really wise boiler operator will be  change its output again. A control loop contains a con-
               able to relate to how the controls work with the boiler  troller, a device to measure the process variable, a source
               and its auxiliaries.                                 of setpoint, an output device that controls the flow and
                    Let’s start with parameter, it’s a quantity, value,  anything else that changes the value of the process vari-
               or constant whose value varies with the circumstances  able or the setpoint.
               of the system. The controller doesn’t know what the      A loop can be as simple as a level controller con-
               parameter is and it doesn’t care. It can be pressure, tem-  sisting of controller with internal setpoint adjustment, a
               perature, level, count, pH, oxygen content in percent,  level transmitter and control valve to similar devices in
               differential pressure, a flow of any fluid, a weight, etc.  combination with a large number of computers located
               The controller basically deals with parameters that are  in different parts of the plant. The practical limit of a
               called inputs and they are used to create an output, or  loop is at the devices that affect the process variable and
               outputs. Inputs are assigned names that indicate what  any one of those devices can be part of another control
               they are in relation to the controller with the two most  loop.
               important ones being process variable and setpoint.      There is always a control range. The values the
                    The process variable is a value representing the  controllers use have an upper and lower limit. The range
               measurement of whatever it is you are trying to main-  of transmitters has to be established to permit reason-
               tain. If it’s a pressure controller it’s the pressure. If it’s  able control and allow for the normal variations in the
               a level controller it’s the level. It’s the control system’s  measured parameter. A range is selected by the applica-
               representation of the actual value of the parameter  tions engineer (the gal or guy that selects and specifies
               you’re trying to control.                            the controls to be used on a job) to ensure the system will
                    The setpoint is a value representing what you want  control properly. What’s the big deal? It’s a question of
               the process variable to be. If you want the boiler pres-  accuracy and stability.
               sure to hold at 100 psig you adjust the setpoint until the     If you are operating a low pressure steam plant,
               parameter represents 100 psig. When properly applied  then a transmitter producing a signal in the range of 0 to
               the controller will indicate it is set at 100 psig and you  30 psig can maintain a pressure of 10 psig plus or minus
               don’t even have to know what the actual value is. Set-  0.15 psi because the transmitter (which typically has an
               points are not always set by you; a setpoint can be the  accuracy of ± 1/2 %) will produce a signal that accurate.
               output of another controller.                        On a plant operating at 3,000 psig a 0 to 4,000 psi trans-
                    We normally describe a setpoint as being “local”  mitter would be accurate to ± 20 psi and that wouldn’t
               when you can adjust it and “remote” when it’s the out-  necessarily be considered accurate control. So the engi-
               put of another controller. Note that the terms don’t relate  neer might use a transmitter that works in the range of
               to what you would consider as local and remote. If you  2,500 to 3,500 psig to get a transmitter accurate within 5
               have to leave the boiler plant and go around the main  psi.
               building to the shed under the water tower to adjust the     Control signals also have a range and each system
               setpoint of the tower’s water level controller it’s still a  normally uses the same signal range for all the devices
               local setpoint even though it’s remote from the boiler  in the system. There are many standard ranges of con-
               plant. If it was a pneumatic setpoint you could install a  trol signals with the most common ones being 3-15 psig
               little regulator and tubing in the boiler plant (local) and  (pneumatic), 0 to 5 volts (electric, electronic), 4 to 20
               extend the tubing out to the shed under the water tower  milliamps (electronic). Several other signal ranges were
               to produce a… well, I’m sorry to say it but it’s still a local  used and it’s not uncommon to encounter a mix of these
               setpoint. As you’ll see later, a remote setpoint can come  ranges within systems that are a mix of old and new in-
               from a controller right beside the next one in the control  struments and controllers. Other signal ranges you may
               panel so don’t confuse local and remote with location.  encounter are 0 to 30 psig, 0 to 60 psig, and 3 to 27 psig
                    Now we can define a loop. We use the term loop to  pneumatic, 0 to 10 volt, -5 to + 5 volt, 0 to 12 volt, and
               describe parts of a control system because each control  0 to 24 volt values on electrical and electronic systems.
               loop is like a circle; there’s no end to it. The parameter  There are others but their use is industry specific and
   376   377   378   379   380   381   382   383   384   385   386