Page 410 - Boiler_Operators_Handbook,_Second_Edition
P. 410

Controls                                                                                            395


               label can be inappropriate. I’ll call them self-checking  burner management system. The system then waits for
               when they contain a device that blocks the light from the  the prescribed period of time for a purge.
               sensor at intervals and the detector circuit has to sense a     Some are set with fixed timing but modern units
               no flame signal during that interval. Some scanners sim-  have provisions for setting the purge time to comply
               ply block the light at regular intervals so the detector cir-  with the code requirements. The controller supervises
               cuit can determine a flame is present because the signal  the purge by requiring the damper open or purge air
               from the scanner is constantly swinging to produce an  flow switch contacts remain closed during the purge
               alternating current. A constant signal from the scanner  period. Some will simply restart the purge timing if the
               indicates no flame or scanner failure including failure  input is interrupted while others will stop the start up.
               of the self checker. Self checking of scanners shouldn’t  Once the purge timing is complete the contacts for high
               be confused with self checking of the flame detector cir-  fire are opened and another set close to instruct the fir-
               cuitry which is different.                           ing rate controls to go to a low fire position for ignition.
                    Someone will also come up with a device and call  When the firing rate controls are at low fire they close
               it self checking by virtue of some software scheme. I  a low fire position (or ignition permissive where low
               spent several hours fooling with some smoke indicators  fire is lower) switch contacts to provide an input to the
               years ago and found they tested well but didn’t indicate  burner management system.
               the smoke I could see by looking at the top of the stack.     During all of that portion of the start-up sequence
               Their scheme for calibrating a black stack consisted of  the scanner should be looking for a flame. If it sees one
               shorting out a terminal on the sensor, not turning off the  the system should lock out. The reasons can be anything
               light at the other end of the stack. When I finally decided  from defective scanners to oil dripping out of a gun and
               the system wasn’t turning the light off and put a blank  lighting to glowing hot  refractory  from the  previous
               in front of it the indicator happily showed a clear stack!  firing. On more than one occasion an operator figured
               If the scanner doesn’t block the sensor’s view of the fire  out that he could prevent the lockout by pulling out the
               it isn’t a self-checking scanner.                    scanner and covering it with his glove during the purge
                    A self-checking circuit simply confirms a flame  and low fire positioning. Needless to say, he didn’t have
               isn’t detected when it shouldn’t be. Of course I’ve dis-  any accurate flame sensing and eventually an explosion
               covered several systems that were installed and con-  occurred. If that scanner thinks it sees a flame where
               nected in such a manner that the self checking functions  there isn’t one it’s not safe to operate that boiler.
               of the circuit were not allowed to work. If, on a burner     With low fire position proven the controller closes a
               that’s turned off, your scanner doesn’t detect a flame on  contact to energize an electric spark in the ignitor and an-
               a candle or cigarette lighter that you hold in front of it  other contact to energize the ignitor gas shut-off valve(s)
               (you have to remove it from its mount) and it doesn’t  (if the burner is equipped with an ignitor). The controller
               alarm and lock out as a result, yours is one of those.  then waits ten seconds to see if the valves open to admit
               Since many of them were only found after a boiler explo-  gas that is lit by the spark to create an ignitor flame. If the
               sion I urge you to perform that test. If the system doesn’t  flame isn’t detected in that time it stops operation and
               lock out it isn’t safe.                              energizes an alarm horn. If the flame is detected it closes
                    The typical BMS (burner management system)  another contact to energize the main fuel valves. Some
               provides for automatic operation of the burner, per-  also de-energize the electric spark. At a prescribed time
               forming all the steps described in the section on boiler  after the main fuel valves are open it de-energizes the ig-
               start-up. When a pressure control switch closes the BMS  nitor gas valves. If a flame remains detected the controller
               should first determine there is no flame in the burner.  opens the low fire contact and closes an automatic contact
               Provided operating limits like low water cutoff, high  to permit automatic operation of the modulating controls
               steam pressure and low fuel pressure are all satisfied  to control the firing rate.
               (contacts closed in a series circuit) it closes an output     How it did it in the early days was clumsily and
               contact to start the burner fan or fans. When air flow is  with a lot of errors. The timing was all controlled by a
               proven by closing contacts on an air flow switch the fir-  timer motor powering a shaft with several epoxy im-
               ing rate control system is instructed to increase damper  pregnated fiber discs on it that served as cams. Each cam
               position to high fire. Some systems may include provi-  had a flat metal spring riding on it and that spring made
               sions to start an oil pump and prove it operating as  contact with another one where the cam was notched.
               well. The open damper or a purge air flow switch senses  The program was initiated when the boiler’s pressure
               purge air flow to close a contact for another input to the  control switch closed to energize the motor to start rotat-
   405   406   407   408   409   410   411   412   413   414   415