Page 411 - Boiler_Operators_Handbook,_Second_Edition
P. 411

396                                                                               Boiler Operator’s Handbook


               ing the cam assembly. As the cams rotated a change in  failure in the burner management system should also
               the diameter of one would drop its spring to close the  act to safely shut down the boiler or, if it’s failure does
               motor circuit and another closed in the modulating mo-  not present an immediate danger, prevent a subsequent
               tor circuit to drive the controls to high fire. Another con-  start-up of the burner.
               tact then opened to stop the cam drive motor. Once the     Of the many boiler explosions I’ve investigated
               modulating motor got to high fire it closed its high fire  only two were found to occur during operation, the rest
               interlock contact which bypassed the open cam contact  occurred on start-up and problems with the system ar-
               and restarted the cam drive motor beginning the purge  rangement (design) or an alteration of the design could
               timing.                                              be attributed to the explosion. Unlike airplane accidents
                    I won’t explain the whole operation, you’ll figure  where the reason is regularly attributed to pilot error
               the rest out if you happen to get in a plant that’s old  I don’t find operator error to be a primary reason for
               enough to still have one (I doubt it) and you’ll want to re-  a boiler explosion. Many times the operator is present
               place it anyway. Those cam contacts were always a prob-  and doing something but that doesn’t mean the system
               lem because the springs would stretch and get weak and  operated flawlessly, usually the system prevented proper
               the contacts on them would get dirty so they wouldn’t  operation.
               complete a circuit (a boiler room wasn’t that clean in the     Those of us that design the burner management
               good old days) and lower priced microprocessor units  systems have a directive to make the system “damn
               have replaced most of them. You can’t access the program  fool proof and moron approved” so it’s supposed to be
               or fix the microprocessor based units so you simply re-  virtually impossible for operators to create an explosive
               place them; it saves you fooling with those springs and  condition unless they intentionally defeat limits and in-
               cleaning those contacts about once a month.          terlocks. Don’t get me wrong, I’ve seen many a bypassed
                    One last comment on the old cam operated con-   interlock or limit switch. Why was it bypassed? Because
               trollers; there was always a dial connected to the cam  the damn burner wouldn’t work if it wasn’t!
               shaft. The dial looked something like the bottom of an     Speaking of those limits and interlocks reminds
               aluminum can that was cut off and it had numbers on it  me of the many ways they can fail to do what they’re
               that corresponded to the timing of the motor so it could  supposed to, mostly because of improper design or ap-
               be checked. There was also a large black dot on the dial  plication. Every other facility I visit for the first time is
               that indicated where the timer was to stop for normal  usually set up with minimum air flow limits and purge
               firing operation. The beginning of the cycle, which was  air flow switches that, quite frankly, don’t work. It’s be-
               also where the timer stopped when the boiler shut down  cause they don’t sense flow, they only sense pressure.
               for any reason was always marked with a zero. The ex-     I’m sure you’ve seen many burner assemblies
               planation of the cam operated switches and timing does  where the air flow switches are air pressure switches
               help explain some of the instructions for the micropro-  with one side connected to a burner windbox. Any
               cessor based equipment because they were written to  burner windbox, however, normally has burners with
               help us old farts relate to what was going on in that new  air registers that can shut off the flow. Even if they don’t
               black box.                                           a blockage in the boiler will ensure pressure to actuate
                    One of the most important elements of the burner  those switches. I’ve seen many an installation where the
               management control is the checking provisions. The  operators closed the burner registers to produce enough
               burner management controller had to include at least  pressure in the windbox to trip the purge air flow
               two relays, a power relay and a flame relay. The power  switch. Needless to say, if the registers are closed there
               relay could only be energized via a normally closed  is no way to get purge air flow. I prefer air flow switch
               contact on the flame relay (proving the flame relay was  installations that measure the air flow, normally simply
               de-energized) and it closed a normally open contact to  sensing the pressure at the fan inlet as shown later for
               bypass the flame relay contact to continue operation.  adding air flow metering. See initial boiler start-up for
               Once  the  power  relay  was  up  the  flame  relay  closed  more clues on proper operation of burner management
               its contacts to power the main fuel valves and stop the  controls.
               timer motor.                                             The key actions for a wise operator when it comes
                    Any indication of a flame when there isn’t sup-  to burner management is 1) know what they’re sup-
               posed to be one can mean the burner will continue to  posed to do, 2) shut the boiler down when they don’t
               operate when there is no flame present, generating an  do it, 3) Report inconsistencies in operation and regular
               explosive atmosphere in the boiler. Any component  interruptions in operation, 4) don’t change switch or po-
   406   407   408   409   410   411   412   413   414   415   416