110 Boiler Plant and Distribution System Optimization Manual
———————————————————————— ————————————————————————
Tuning Boiler Controls Tuning Boiler Controls
Measurement and Control Response Time Superheat and Reheat Thermocouples
1. Fast measurements improves quality and sta-
bility of control loops • Check for good thermocouple contact with the
bottom of the thermowell
2. Fast response times improves quality and sta-
bility of control loops • At 80% load increase spray valve position 5%
as a step function. Observe steam temperature
3. Valve stroking rates of 2 to 3 seconds Is re- time constant.
quired in many cases.
• Time constant should be less than 30 seconds.
4. If one loop Is upsetting other loops, a compro-
mise must be reached ————————————————————————
Figure 9.4—Tuning boiler controls, superheat and
5. In the final analysis, good engineering judg- reheat thermocouples
ment Is required for tuning loops
————————————————————————
————————————————————————
Figure 9.39—Tuning boiler controls, measurement
and control, response time
Tuning Boiler Controls
Steam Temperature Control
• Fast accurate temperature measurements are
————————————————————————
desirable
Tuning Boiler Controls • Slow temperature constants can be compen-
PID sated for with derivative action at the tem-
Proportional Gain-Reset-Derivative perature controller
• It is desirable to use as little PID as possible ————————————————————————
Figure 9.42—Tuning boiler controls, steam tempera-
• Stability Is more Important than quality of ture control
control
• Excessive reset action is deadly for most con-
————————————————————————
trol loops
Tuning Boiler Controls
————————————————————————
Figure 9.40—Tuning boiler controls, PID proportion-
Adaptive Tuning
al gain -Reset-Derivative
• Final steam temperature controller must be
tuned at 5 points.
————————————————————————
Figure 9.43—Tuning boiler controls, adaptive tuning