110                                                 Boiler Plant and Distribution System Optimization Manual


                ————————————————————————                            ————————————————————————

                            Tuning Boiler Controls                               Tuning Boiler Controls
                     Measurement and Control Response Time                 Superheat and Reheat Thermocouples


                   1.  Fast measurements improves quality and sta-
                       bility of control loops                          •  Check for good thermocouple contact with the
                                                                           bottom of the thermowell
                   2.  Fast response times improves quality and sta-
                       bility of control loops                          •  At 80% load increase spray valve position 5%
                                                                           as a step function. Observe steam temperature
                   3.  Valve stroking rates of 2 to 3 seconds Is re-       time constant.
                       quired in many cases.
                                                                        •  Time constant should be less than 30 seconds.
                   4.  If one loop Is upsetting other loops, a compro-
                       mise must be reached                         ————————————————————————
                                                                    Figure 9.4—Tuning boiler controls, superheat and
                   5.  In the final analysis, good engineering judg-  reheat thermocouples
                       ment Is required for tuning loops

                ————————————————————————
                                                                    ————————————————————————
                Figure 9.39—Tuning boiler controls, measurement
                and control, response time
                                                                                 Tuning Boiler Controls
                                                                                Steam Temperature Control

                                                                        •  Fast accurate temperature measurements are
                ————————————————————————
                                                                           desirable

                            Tuning Boiler Controls                      •  Slow temperature constants can be compen-
                                      PID                                  sated for with derivative action at the tem-
                        Proportional Gain-Reset-Derivative                 perature controller

                   •  It is desirable to use as little PID as possible  ————————————————————————
                                                                    Figure 9.42—Tuning boiler controls, steam tempera-
                   •  Stability Is more Important than quality of   ture control
                       control

                   •  Excessive reset action is deadly for most con-
                                                                    ————————————————————————
                       trol loops
                                                                                 Tuning Boiler Controls
                ————————————————————————
                Figure 9.40—Tuning boiler controls, PID proportion-
                                                                                     Adaptive Tuning
                al gain -Reset-Derivative
                                                                        •  Final steam temperature controller must be
                                                                           tuned at 5 points.

                                                                    ————————————————————————
                                                                    Figure 9.43—Tuning boiler controls, adaptive tuning