Page 124 - Boiler plant and distribution system optimization manual
P. 124

Boiler Tuneup                                                                                     109



                                                                    ————————————————————————
                                                                                 Tuning Boiler Controls
                                                                        Large, Interactive, Non-linear Control Loops


                                                                         Important Impacts
                                                                         •  Efficiency
                                                                         •  Ramp Rate
                                                                         •  Turndown
                                                                         •  Low load operations
                                                                         •  Unit availability
                                                                         •  Ability to survive upsets and equipment fail-
                                                                            ures
                                                                    ————————————————————————
                                                                    Figure 9.36—Tuning boiler controls, important im-
                Figure 9.34—This figure shows that differences exist   pact
                between the performance of individual burners, the
                reasons should be established and corrected if pos-
                sible.                                              ————————————————————————


                ————————————————————————                                         Tuning Boiler Controls
                 The Reasons for Deviations Between Burners              Basics
                                                                    •    Start from the bottom up
                   1.  Gas. Gas port dimension differences & Piping
                                                                         —  Control drives
                       differences
                                                                         —  Valve operators
                   2.  Oil. Atomizer port tolerances, surface finish &   —  Final control elements
                       erosion. Piping differences.
                                                                    All measurements must be accurate beyond any doubt
                   3.  Air. Variations in air flow to burners.      and backed up by duplicate Instruments

                   4.  Variation in pressure drops across burners.  ————————————————————————
                                                                         Figure 9.37—Tuning boiler controls, basics
                       [Air doors, swirl vanes, flow splitters, surface
                       finish & refractory damage.

                   5.  Wind box symmetry & cross flow.              ————————————————————————

                   6.  Windbox air temperatures and buoyancy forc-               Tuning Boiler Controls
                       es.                                                    Deadband and Repeatability
                ————————————————————————                                       Controlling Process Variables
                Figure 9.35—Reasons for deviations between perfor-
                mance of otherwise identical burners as illustrated   •  No  amount  of  upper  loop  tuning  will  fix  5%
                in Figure 9.34                                          deadband


                                                                    •  Over 3% to 5% deadband is unacceptable
                TUNING BOILER CONTROLS
                                                                        Process variables: feedwater flow, gas flow, air
                     The following section is composed of figures       flow, fuel flow, spray valve, etc.
                which cover the subject of tuning boiler controls.
                They are designed for a classroom presentation      ————————————————————————
                                                                    Figure 9.38—Tuning boiler controls, deadband and
                and make up a simple presentation of a complex
                                                                    repeatability
                subject.