Page 126 - Boiler plant and distribution system optimization manual
P. 126
Boiler Tuneup 111
———————————————————————— ————————————————————————
Tuning Boiler Controls
Tuning Boiler Controls
Feed Forward Signals
Fuel Flow
1. The necessary influence of feed forward sig-
nals should be calculated from steady state • Fuel should never lead air supply
tests.
• Fuel and air should move together
2. No more than 80% - 90% of actual influence
should be set • Adaptive tuning is most often required for
fuel and air to synchronize variations over
———————————————————————— turn-down range
Figure 9.44—Tuning boiler controls, feed forward
signals ( ————————————————————————
Figure 9.47—Tuning boiler controls, fuel flow re-
quirements
————————————————————————
Tuning Boiler Controls
Feed Forward Signals ————————————————————————
Example: superheat spray set point Is 15 F for 100 Tuning Boiler Controls
psi of first stage pressure
Drum Level Stability
— Use only 12 -13 F/100 psi feed-forward sig-
nal • Drum level instability can de-stabilize an en-
tire boiler
— Let feedback control handle last 2 degrees to
eliminate Instability • Smaller drums may need 3-element control
———————————————————————— • Extended range of feedwater and steam flow
Figure 9.45—Tuning boiler controls, feed forward measurement may also be needed to measure
signals low and high range temporary excursions In
boiler operations
———————————————————————— ————————————————————————
Figure 9.48—Tuning boiler controls, drum level sta-
bility
Tuning Boiler Controls
Fuel Flow
• During the first 30 to 90 seconds after a load
change the required energy comes from storage
[boiling water in the drum]
————————————————————————
Figure 9.46—Tuning boiler controls, fuel flow