234                                                 Boiler Plant and Distribution System Optimization Manual













































                          Figure 12.6—Feedwater preheater used to control cold end corrosion in the economizer
                          and acid dew point n the stack. The steam energy used for heating is not lost as it recy-
                          cles back into the boiler as heat in the feedwater.


                Figure 12.7. Relationship be-
                tween initial water vapor dew
                point of flue gasses and the ex-
                cess air level.