240                                                 Boiler Plant and Distribution System Optimization Manual


                perature from 100°F to 110°F.                       the cycle is repeated.
                     The tray type tower has a resistance to gas         A thermosyphon type heat pipe does not uti-
                flow between 0.5 and 1.0 inches of water column     lize a wicking material, instead the pipe is placed
                and an outlet temperature from 130°F to 140°F.      in a vertical position with the condenser placed
                     The  packed  tower  type  has  excellent  heat   above the evaporator section. As the vapor con-
                transfer but also has a high pressure drop in ex-   denses, it returns to the evaporator section by
                cess of 5 to 10 inches water column, but the res-   gravity. Even with wicking material it is advan-
                ervoir temperature is as high as 150°F depending    tageous to locate the evaporator -section-- below
                on conditions.                                      the  condenser  so  condensed  fluid  is  aided  by
                                                                    gravity.
                Heat Pipe                                                Heat pipes have the advantage that they can
                     A heat pipe is composed of a sealed pipe par-  be constructed of corrosion resistant materials.
                tially charged with water, Freon, ammonia or oth-   They are mostly applied to transfer heat from one
                er suitable substance. It can be divided into three   gas stream to another, but have been used suc-
                sections (Figure 12.15), the evaporator section, the   cessfully  in  fluid  streams  also.  The  gas  streams
                adiabatic section and the condenser section.        must be adjacent to each other because of the loss
                     In the evaporator section, heat is absorbed    of performance from routing streams of working
                by  the  internal  working  fluid  by  evaporation.   fluid and vapor through an unusually long adi-
                Pressure differential causes the vapor to           abatic section. Heat pipes can be compact, oper-
                flow to the cooler condensing section where the     ate at low temperature differentials and have no
                latent heat is given up to the cooler environment   moving parts to malfunction.
                condensing the working fluid.
                     The internal circumference of the heat pipe    Plate Type Heat Exchanger
                is lined with a thin layer of wicking or mesh type       Plate type gas-to-gas heat exchangers can be
                material and the working fluid migrates by capil-   used  in  counterflow  or  crossflow  through  adja-
                lary action back to the evaporator section where    cent passages separated by heat conducting walls



































                         Figure 12.13—Direct contact flue gas condensing heat recovery tower with heat exchanger.