The Control of Boilers                                                                             83



                steam bubbles in the drum water which the drum           Boiler  blowdown  water  is  often  passed
                level controller interprets as a need for more      through a heat exchanger to recover the energy
                water, which is colder than the boiler saturation   which would otherwise be wasted. Heat from
                temperature causing further shrinking.              the boiler blowdown is usually used to heat the
                     The three element control loop is very pre-    incoming boiler makeup feedwater.
                cise and stable because of the closed  loop control
                of the feedwater valve. It measures steam flow
                and water flow as well as drum water level. This    FURNACE PRESSURE CONTROL
                system can adjust for actual steam and water flow
                conditions balancing this information against            Furnace pressure conditions must be closely
                measured water level.                               controlled to establish safe and efficient firing
                     Feedwater controllers are available in pneu-   conditions. Air fuel mixing for the burner systems
                matic, analog electric and digital electronic mod-  depends to a great degree on the differential pres-
                els.                                                sure across the burner.
                                                                         Different challenges apply to different siz-
                                                                    es of boilers. Figure 8.11 shows a natural draft,
                BLOWDOWN CONTROL                                    balanced draft, induced draft and forced draft
                                                                    systems. Each configuration will require special
                     Blowdown is done either intermittently or      control considerations.
                continuously. On many smaller boilers blow-              Damper openings, forced draft fans, induced
                down is performed manually after an analysis        draft fans and stack effect all play an important
                of the boiler water indicates that the water is ex-  role in various furnace pressure control systems.
                ceeding impurity limits.
                     If too much hot boiler water is blown down     Steam Temperature Control
                from the boiler an excessive amount of energy is         Superheaters are used to raise the steam
                wasted. If the concentration of impurities in the   temperature above the saturation point for super-
                boiler is allowed to get to high, carry-over and    heated steam. In doing so, the temperature of the
                scale formation can occur.                          superheated steam must be regulated. The main
                     Control systems are available which will au-   control loop is to regulate the superheated steam
                tomatically perform the operations necessary to     temperature by a desuperheater steam valve.
                blow down the boiler.                               This control loop is enhanced by a feed forward,
                Automatic blowdown controllers use electro-         usually air flow, signal into the loop plus an in-
                chemical cells to measure the concentration of      ner loop cascade signal for spray water flow to
                minerals by measuring electrical conductivity       eliminate the effects of spray valve performance
                and acid (PH) levels.                               variations.
                     The signal corresponding to the impurity
                level is compared to the setpoint and when ex-      Cold End Temperature Control
                ceeded, blowdown is initiated.                           Cold end corrosion occurs when metal tem-
                     Boilers operated at a steady load may be       peratures fall below the dew point for sulfurous
                equipped with a continuous blowdown system.         and sulfuric acids. The most critical point for the
                A continuous blowdown system removes a con-         economizer is the feedwater entrance point to
                tinuous, usually small amount, of water from the    the heat exchanger where metal surfaces can be
                steam drum to keep the concentration of undesir-    cooled below the acid dew point.
                able chemicals at a safe level.                          In air preheaters a steam or glycol heating
                     Manual blowdown to remove sludge which         system is used to regulate the cold end tempera-
                has settled in the mud (lower) drum is still neces-  ture. A single element control of the heating con-
                sary.                                               trol valve may be adequate. However, the three