Page 303 - Buried Pipe Design
P. 303

274   Chapter Five

           Thus, the required three-edge bearing service load is defined in
         terms of the D load to produce a 0.01-in crack. The D load required for
         a particular pipe soil installation is determined as


                                         W e   W L   W w
                            (W D load ) 0.01                         (5.14)
                                              B f D i
           The 0.01-in crack criterion is not applicable to nonreinforced con-
         crete pipe. These pipes are at the W 3-edge strength limit when the first
         crack occurs. Although nonreinforced pipe may still be able to perform
         after cracking starts in field installations, a safety factor from 1.25 to
         1.5 is normally provided against flexural cracking at the service load.
         Thus, the required ultimate D load strength for nonreinforced concrete
         pipe is

                                       1.5 (W e   W L   W w )
                          (W D load )  ult                           (5.15)
                                              B f D i
         Note: W L (live load) is frequently neglected when the height of earth fill
         above the pipe is more than 8 ft or the outside pipe diameter,
         whichever is greater.  Note: W w (hydrostatic load) is frequently
         neglected, especially for small-diameter pipe.
           The required ultimate W 3-edge strength for reinforced concrete pipe is
         given by Eq. (5.15), except for the use of a reduced strength factor for
         pipe strength classes higher than class 4. For typical pipe strength
         classes up to class 4, the ultimate strength design limit is 1.5 times the
         required service load W 3-edge strength. This strength factor is 1.25 for
         class 5 pipe strength and is linearly interpolated between 1.5 and 1.25
         for any strength classes between 4 and 5. An ultimate strength design
         limit is also defined for reinforced concrete pipe designed by the indi-
         rect design procedure. Such a design limit is included in ASTM speci-
         fications for reinforced concrete pipe.
           Design requirements for nonreinforced pipe with specified  W 3-edge
         strength requirements are given in  ASTM C 985. Design  W 3-edge
         strengths for nonreinforced concrete pipe having various standard
         diameters and wall thicknesses are given in ASTM C 14. The D load
         definition of three-edge bearing strength is not used in this standard.
           Design requirements for reinforced pipe with specified  D load
         strength requirements and special reinforcement designs are given in
         ASTM C 655. Design W 3-edge strengths for reinforced concrete pipe hav-
         ing various standard diameters, wall thicknesses, concrete strengths,
         and reinforcement requirements for standard strength classes are
         given in ASTM C 76, C 506, and C 507.
           Specifying agencies sometimes require  W 3-edge tests for proof of
         design. More frequently, they may require W 3-edge tests for proof of quality