Page 126 - Defrosting for Air Source Heat Pump
P. 126

Investigation of effect on uneven defrosting performance          119


                           To compressor                    Heating mode  Side B
                           From compressor   To EEV         Defrosting mode
                                             From EEV
                          Header                        650 mm
                                                                        44 mm
                                 T e
                                                 Circuit 3
                                MV 3
                             T i
                               SV 3
                          T e
                                          Circuit 2  Wind board
                          MV 2                                  326 mm
                      T i                                               Side C
                        SV 2                                     Meltedfrost
                     T e                                          700 mm
                                    Circuit 1
                    MV 1                                   22 mm
                 T i
                  SV 1                                 152 mm
               Distributor        590 mm
                                    Side A  Melted frost
                                       750 mm
                  Water collecting tray  Water collecting cylinder
                     (slope 37  )    (2000 mL)
           Fig. 5.2 Details of the horizontally installed three-circuit outdoor coil and locations of SVs
           and MVs.

           preweighed cotton tissues. In this way, the melted frost from the outdoor coil during
           defrosting was collected and weighed. The specifications of the three-parallel refrig-
           erant circuit outdoor coil are shown in Table 5.1.
              Fig. 5.3 shows the airside details of the outdoor coil in the experimental ASHP unit
           installed in the outdoor frosting space. On the windward side (Side C in Figs. 5.1–5.3),
           the air dry-bulb temperatures were measured at 6 points using thermocouples (Type K,
           of  0.75% accuracy) and the air wet-bulb temperatures at 3 points using temperature
           sensors (PT100, class A). In this way, there were two dry-bulb temperature sensors
           and two wet-bulb temperature sensors for each circuit. As seen in Fig. 5.3, they were
           placed at the same positions for each circuit. The average values from these measure-
           ments were used as the inlet air dry-bulb temperature and the wet-bulb temperature in
           the following calculations. On the other hand, the air temperature and humidity down-
           stream of the outdoor coil were measured by a hygrosensor (  0.2°C and  1.0% RH
           accuracy, respectively; the Testo Hygrotest 650 was located inside an air duct 700 mm
           downstream of the outdoor coil outlet. To ensure the best possible measuring accu-
           racy, the air wet-bulb temperature sensors positioned on Side C of the outdoor coil
           were also calibrated using the hygrosensor. Furthermore, the air flow rate passing
           through the outdoor coil was measured by using a flow hood (of  3% accuracy) with
           a 16-point velocity grid located at the center of a 400 mm   400 mm air duct 600 mm
           long, as shown in Fig. 5.3.
              Precalibrated K-type thermocouples were also used for measuring the temperatures
           of the tube/coil and fin surfaces of the outdoor coil. Six were for measuring the refrig-
           erant tube surface temperatures at both the inlets (T i in Fig. 5.2) and exits (T e in
           Fig. 5.2) of the three refrigerant circuits. Three were affixed on the fin surface at
           the center of each circuit. These fin surface temperature sensors are located at the
   121   122   123   124   125   126   127   128   129   130   131