Page 128 - Defrosting for Air Source Heat Pump
P. 128

Investigation of effect on uneven defrosting performance          121

           upward surface of the outdoor coil, the opposite side to Side C, so that the measured fin
           surface temperatures can avoid the effects of downward-flowing melted frost during
           defrosting. Furthermore, one more thermocouple was placed inside the water-
           collecting cylinder to measure the temperature of the melted frost collected, as shown
           in Fig. 5.2. On the other hand, for the experimental ASHP unit, refrigerant pressures
           were measured using pressure transmitters (Danfoss Pressure Transmitter, Type AKS
           32 and AKS 33) with an accuracy of  0.3% of full scale reading and refrigerant vol-
           umetric flow rate by a variable area flow meter with a reported accuracy of  1.6% of
           full scale reading (KROHNE VA Flowmeter, H250). All sensors and measuring
           devices were able to output a direct current signal of 4–20 mA or 1–5 V, which
           can be transferred to a data acquisition system (DAS) for logging and recording.
           The DAS collected and recorded all the measured data throughout both frosting
           and defrosting at an interval of 5 s. In addition, during defrosting, photos for surface
           conditions of the outdoor coil were taken at an interval of 10 s.

           5.2.1.2 Experimental procedures and conditions
           Prior to the defrosting operation, the experimental ASHP unit was operated in the
           heating (frosting) mode for 60 min at an outdoor frosting ambient temperature of
           0.5   0.2°C (dry-bulb temperature) and 90   3% relative humidity, which was jointly
           maintained by the use of both the experimental ASHP unit and the LGUs placed in the
           outdoor frosting space. During heating (frosting), the air temperature inside the heated
           indoor space was maintained at 20   0.5°C, which was jointly maintained by the use
           of both the experimental ASHP unit and the existing A/C system. The experimental
           conditions are summarized in Table 5.2.
              Before defrosting was started, the compressor was first switched off. One minute
           after the compressor shutdown, the four-way valve was switched to defrosting mode.
           Four seconds later, the compressor was powered on again manually, and a defrosting
           operation was started. The defrosting operation was also manually terminated.
           However, different from the previous experimental studies introduced in Chapter 3,
           the defrosting operation was terminated when the tube surface temperature at the
           exits of the three refrigerant circuits in the outdoor coil all reached the preset


            Table 5.2 Experimental conditions
            Item    Parameter                                  Value      Unit
            1       Air temperature in indoor heated space     20         °C
            2       Air temperature in outdoor frosting space  0.5   0.2  °C
            3       Air relative humidity in outdoor frosting space  90   3%  –
            4       Face velocity of outdoor coil              1.3 a      ms  1
            5       Face velocity of indoor coil at defrosting mode  2.31  m s  1
            6       Face velocity of indoor coil at heating (frosting) mode  3.68  m s  1
            7       Heating (frosting) operation duration      60         min

            a
            The average value during a heating (frosting) operation. During heating (frosting), the face velocity decreased due to
            frost growth.
   123   124   125   126   127   128   129   130   131   132   133