Page 130 - Defrosting for Air Source Heat Pump
P. 130

Investigation of effect on uneven defrosting performance          123

           the frost evenly accumulate on the surface of the outdoor coil, as many parameters
           affect frosting performance [24]. However, in this section, modulating valves installed
           at the inlet refrigerant pipe to each circuit (as shown in Fig. 5.2) were deployed to vary
           the refrigerant flow to each circuit adjusted. Therefore, the frost accumulation on the
           surface of the three circuits was close to each other, with their biggest difference being
           less than 10% [11, 25, 26]. Second, to make the comparative study results meaningful,
           the frost accumulations in different cases should be close to each other. Therefore, in
           this section, the frosting duration was fixed at 60 min, as listed in Table 5.2. The frost
           accumulations could be calculated with the total mass of the melted frost collected,
           with the water vaporized into the ambient air during defrosting neglected.
              Fig. 5.4 shows the force analysis of retained water droplets on the surface of the
           outdoor coil, on the conditions of (a) on the side of a single fin, (b) between double
           fins, and (c) at the bottom of the fins. Four types of force—gravity force (G), fraction
           force (F f ), normal force (N), and surface tension (F s )—would work on the water drop-
           lets. As the frost melted during defrosting, the melted frost would be held on the fin
           surface due to surface tension. As the water accumulated, the gravity effects of water
           increased. The melted frost would flow downward when its gravity exceeded the max-
           imum surface tension [23]. When a vertical outdoor coil was horizontally installed,
           blowing the melted frost may be one of methods to increase the melted frost flowing
           away. As shown in Fig. 5.4, after the force of wind blowing (F w ) is added, the max-
           imum surface tension was easy to exceed.
              Therefore, to comparatively and quantitatively study the defrosting performance of
           an ASHP unit having a horizontal multicircuit outdoor coil, Case 1 and Case 2 were
           designed and carried out in this section. In the two cases, the outdoor coils were ver-
           tically and horizontally installed, respectively. Therefore, their experimental results
           could be meaningfully compared. Furthermore, to study the effects of blowing the
           melted frost by reversing the outdoor air fan, Case 3 was also designed and conducted.
           In Case 3, the outdoor air fan was turned on and reversed blowing by a control strategy
           adjustment during defrosting when the tube surface temperature of one circuit reached
           3°C, and the blowing was kept up for approximately 40 s. In this method, the wind was
           expected to blow the melted frost away by destroying its surface tension. Therefore,
           the effects of wind blowing could be conducted by comparative analysis of the

                        Fin                  Fin                  Fin

                        F f Droplet         F f
                                             Droplet
                  F s     F b        F s     F s
                        G                   G             F s F s  F s  Droplets
                        F w                  F w
                                                        G
                                                                F w
                  (A)             (B)                 (C)

           Fig. 5.4 Force analysis of retained water droplets on the surface of the outdoor coil. (A) On side
           of single fin. (B) Between double fins. (C) At the bottom of fins.
   125   126   127   128   129   130   131   132   133   134   135