Page 232 - Defrosting for Air Source Heat Pump
P. 232

Energy transfer during defrosting                                 227


            Table 8.1 Specifications of the tailor-made three-circuit outdoor coil
            Item        Parameter                          Value           Unit

            1           Height of the outdoor coil         500             mm
            2           Width of the outdoor coil          590             mm
            3           Thickness of the outdoor coil      44              mm
            4           Fin height                         152.4           mm
            5           Fin width                          44              mm
            6           Fin thickness                      0.115           mm
            7           Fin pitch                          2.1             mm
            8           Fin type                           Plate           –
            9           Tube external diameter             10              mm
            10          Tube thickness                     0.5             mm
            11          Tube spacing                       20              mm
            12          Circuit pitch                      22              mm
            13          Number of tube rows                2               –
            14          Number of circuits                 3               –
            15          Number of water-collecting trays   3               –
            16          Number of water-collecting cylinders  3            –
            17          Number of wind boards              2
            18          Material of tube                   Copper          –
            19          Material of fin                    Aluminum        –
            20          Material of wind board             Wood
            21          Material of water-collecting tray  PVC             –
            22          Material of water-collecting cylinder  PVC         –
            23          Volume of cylinder A, B, and C     500             mL
            24          Volume of cylinder D               2000            mL





            Table 8.2 Specifications of the prototypical three-circuit indoor coil
            Item   Parameter                   Value                       Unit
            1      Number of circuits          3                           /
            2      Number of tube rows in each  Circuits 1, 2: 6   2; Circuit 3:  /
                   circuit                     4   2
            3      Tube spacing                5                           mm
            4      Length of indoor coil       103                         cm
            5      Fin type                    Wavy                        /
            6      Fin length                  Circuits 1, 2: 125; Circuit 3: 85  mm
            7      Fin width                   25                          mm
            8      Fin pitch                   1.3                         mm
            9      Fin thickness               0.08                        mm
            10     Tube external diameter      7                           mm
            11     Material of fin             Aluminum                    /
            12     Material of tube            Copper                      /
   227   228   229   230   231   232   233   234   235   236   237