Page 314 - Defrosting for Air Source Heat Pump
P. 314

Technoeconomic performances                                       309


            Table 10.5 Experimental results of the four defrosting cases
            Item   Parameters                                 Case D1   Case D2

            1      FEC                                        82.6%     96.6%
            2      Total frost accumulation                   878 g     881 g
            3      Defrosting duration                        205 s     185 s
            4      Total power inputs to compressor and indoor air fan  124.6 kJ  107.6 kJ
            5      Energy from indoor air                     666.1 kJ  541.2 kJ
            6      Condition shown in Fig. 10.2               (A)       (B)
            7      Shown in Fig. 10.4                         (T1)      (T2)

           FEC 3 ¼82.6%. This condition was reached by fully opening the valves, and this case
           works as the ASHP unit without valves installed in this economic analysis study.
              Some experimental results of the two defrosting cases were listed in Table 10.5.
           Their total frost accumulations were 878 and 881 g, which were nearly the same.
           The frosting durations were all 60 min, but their defrosting durations were 205 and
           185 s, respectively. To undertake this economic analysis work, the total power input
           to compressor and indoor air fan and the thermal energy from the indoor air were also
           calculated and presented.


           10.2.1.2 Assumptions and calculation conditions

           To economically analyze the frosting and defrosting performances of the new ASHP
           unit with valves installed, four kinds of assumptions were given: (1) fundamental
           assumptions, (2) frosting assumptions, (3) defrosting assumptions, and (4) cooling
           assumptions. The first one was assumed for all operating seasons, and the following
           three kinds for different operating seasons. Additionally, in order to clearly show the
           frosting and defrosting influence on economic performance of the modified ASHP
           unit, a typical severe cold city, Harbin in China, was taken as the operation location.
           (1) Fundamental assumptions
           In this economic analysis, the following fundamental assumptions were first given:
             i. Maintenance costs of equipment were neglected.
             ii. Running cost of solenoid valves was neglected.
            iii. Service life of the ASHP unit was assumed at 15 years.
            iv. In the whole service life of an ASHP unit, three seasons were divided: heating season with
               frost formation, heating season without frost formation, and cooling season.
             v. Durations of the three operating seasons were constant, and assumed as the climate of
               Harbin in northeast China.
            vi. Heating season was from Nov. 1 to Mar. 31, when the minimum average air temperature
                            o
               was lower than 0 C (Shown in Fig. 10.5).
            vii. Cooling season was from Jun. 1 to Jul. 31, when the maximum average air temperature
                             o
               was higher than 26 C (Shown in Fig. 10.5).
           viii. In heating season with frost formation, a frosting/defrosting cycle was assumed at 70 min.
   309   310   311   312   313   314   315   316   317   318   319