316                                         Defrosting for Air Source Heat Pump

         Stage 2: Heating season without frost formation
         When the ASHP unit works in heating season without frost formation, the total run-
         ning cost, C r, NFDH , includes three parts of the electricity cost: (1) electricity cost of the
         compressor, C r, comp, h , (2) electricity cost of the indoor air fan, C r, id, fan , and (3) elec-
         tricity cost of the outdoor air fan, C r, od, fan :

                                                                       (10.21)
             C r,NFDH ¼ C r,comp,NFDH + C r,id, fan + C r,od, fan
         The three unknown parameters could be calculated by,

                                                                       (10.22)
             C r,comp,NFDH ¼ C e,unit  P NFDH  T Y  T NFDH  T ODH
             C r,id, fan ¼ C e,unit  P id, fan  T Y  T NFDH  T ODH     (10.23)

             C r,od, fan ¼ C e,unit  P od, fan  T Y  T NFDH  T ODH     (10.24)

         In Eqs. (10.22)–(10.24), T ODH was the operating duration in the heating season with-
         out frost formation, assumed at 12 h in this study. Considering the Eqs. (10.21)–
         (10.24), the total running cost in the heating season without frost formation could
         be evaluated by,


                                                                       (10.25)
             C r,NFDH ¼ C e,unit   P NFDH + P id, fan + P od, fan  T Y  T NFDH  T ODH
                      Q id,air,NFDH
             C r,NFDH ¼                                                (10.26)
                      COP NFDH
         where the thermal energy supplied to the indoor air during frosting operation and the
         COP in this season, Q id, air, NFDH and COP NFDH , were also obtained from the previous
         frosting experiments.


         Stage 3: Cooling season
         The total running cost for the ASHP unit in the cooling season, C r, C , consists of the
         electricity cost of the compressor, C r, comp, C , the electricity cost of the indoor air
         fan,C r, id, fan , and the electricity cost of the outdoor air fan, C r, od, fan :

             C r,C ¼ C r,comp,C + C r,id, fan + C r,od, fan            (10.27)

         In Eq. (10.27), the same as those in Eq. (10.21), the three unknown parameters were
         evaluated by,

                                                                       (10.28)
             C r,comp,C ¼ C e,unit  P C  T Y  T CD  T ODC
                                                                       (10.29)
             C r,id, fan ¼ C e,unit  P id, fan  T Y  T CD  T ODC
                                                                       (10.30)
             C r,od, fan ¼ C e,unit  P od, fan  T Y  T CD  T ODC