Page 60 - Defrosting for Air Source Heat Pump
P. 60

Uneven defrosting on the outdoor coil in an ASHP                   51























           Fig. 3.4 Airside details of the outdoor coil in the experimental ASHP unit.

           the melted frost collected. In addition, pressure transmitters having an accuracy of
            0.3% of the full scale reading were used to measure refrigerant pressures. The mass
           flow rate of refrigerant was measured by a variable-area flow meter with an accuracy
           of  1.6% of the full scale reading. All sensors/measuring devices can output a direct
           current signal of 4–20 mA or 1–5 V. In addition, during defrosting, photos were taken
           at an interval of 10 s to visually record the conditions of frost melting on the surface of
           the outdoor coil.

           3.2.1.2 Experimental conditions and procedures
           Prior to the defrosting operation, the experimental ASHP unit was in operation at
           frosting (heating) mode for 1 h, at the frosting ambient temperature of 0.5   0.2°C
           (dry-bulb temperature) and 90%   3% RH. This was achieved by the joint use of both
           the LGUs and the experimental ASHP unit placed in the outdoor frosting space.
              Before beginning defrosting, the compressor was turned off first. Then, after 1 min,
           the four-way valve was changed to defrost mode. Four seconds later, the compressor
           was switched on again, and thus a defrost operation was commenced. The defrost
           operation was ended manually when the temperature of the tube surface at the exit
           of the lowest refrigerant circuit of the outdoor coil arrived at 24°C [5–10]. The outdoor
           air fan was switched off during defrosting, but the indoor air fan remained in operation
           at a lower speed. During frosting, the air temperature in the heated indoor space was
           kept at 20°C. This was achieved by the joint use of both the existing A/C system and
           the experimental ASHP unit. Table 3.2 shows the experimental conditions.



           3.2.2 Experimental cases
           A series of experimental works using the experimental ASHP unit have been carried
           out to examine the effects of the downward flow of the melted frost over the outdoor
           coil surface due to gravity. Various combinations of refrigerant circuits, from two
   55   56   57   58   59   60   61   62   63   64   65