Page 68 - Defrosting for Air Source Heat Pump
P. 68

Uneven defrosting on the outdoor coil in an ASHP                   59


            Table 3.4 Specifications of the tailor-made three-circuit outdoor coil
            Item        Parameter                          Value           Unit

            1           Height of the outdoor coil         500             mm
            2           Width of the outdoor coil          590             mm
            3           Thickness of the outdoor coil      44              mm
            4           Fin height                         152.4           mm
            5           Fin width                          44              mm
            6           Fin thickness                      0.115           mm
            7           Fin pitch                          2.1             mm
            8           Fin type                           Plate           –
            9           Tube external diameter             10              mm
            10          Tube thickness                     0.5             mm
            11          Tube spacing                       20              mm
            12          Circuit pitch                      22              mm
            13          Number of tube rows                2               –
            14          Number of circuits                 3               –
            15          Number of water-collecting trays   3               –
            16          Number of water-collecting cylinders  3            –
            17          Number of wind boards              2
            18          Material of tube                   Copper          –
            19          Material of fin                    Aluminum        –
            20          Material of wind board             Wood
            21          Material of water-collecting tray  PVC             –
            22          Material of water-collecting cylinder  PVC         –
            23          Volume of Cylinder A, B, and C     500             mL
            24          Volume of Cylinder D               2000            mL



            Table 3.5 Measurement/calculation errors of system parameters

                                                     Measurement/
            Item   Parameter                         calculation error     Unit
            1      Air dry-bulb temperature at upstream of   1 (K-type     °C
                   the outdoor coil                  thermocouple)
            2      Air wet-bulb temperature at upstream of   0.1 (PT100, class A)  °C
                   the outdoor coil
            3      Air temperature at downstream of the   0.2 (hygrosensor)  °C
                   outdoor coil
            4      Air relative humidity at downstream of the   1.0% (hygrosensor)  –
                   outdoor coil
            5      Air flow rate passing through the outdoor   3% (flow hood)  –
                   coil
            6      Temperatures of tube/coil and fin surfaces   1 (K-type  °C
                                                     thermocouple)
            7      Refrigerant pressure               0.3% (pressure       –
                                                     transmitters)
                                                                        Continued
   63   64   65   66   67   68   69   70   71   72   73