64                                          Defrosting for Air Source Heat Pump



























         Fig. 3.16 Measured fin temperatures at the center of the three refrigerant circuits during
         defrosting in Case 1.



























         Fig. 3.17 Measured fin temperatures at the center of refrigerant circuits in Case 2.


         reached 24°C almost at the same time, at 167, 166, and 168 s, respectively. The time
         differences of 6 and 18 s in Case 2 and Case 3 compared to that in Case 1 clearly
         showed that it would take longer for the bottom circuit to reach 24°C when fewer trays
         were installed, so that a defrosting operating was prolonged and more energy
         consumed.