Page 76 - Defrosting for Air Source Heat Pump
P. 76

Uneven defrosting on the outdoor coil in an ASHP                   67

              Defrosting efficiency can be used to evaluate the performance of a defrosting oper-
           ation. It is defined as the ratio of the actual amount of energy consumption required to
           both melt the accumulated frost and vaporize the retained melted frost to the total
           amount of energy available from an outdoor coil during an entire defrosting operation,
           as follows:

                       E m + E v
               η ¼                                                         (3.1)
                d
                   Q com  + Q fan + Q air
           where E m and E v are the total heat used for melting frost and vaporizing the retained
           water, respectively, and they are evaluated by:

               E m ¼ M f L sf                                              (3.2)
               E v ¼ M v L v                                               (3.3)
           where M f and M v are the total mass of the frost formed on the outdoor coil and the mass
           of vaporized melted frost, respectively, and L sf and L v the latent heat of frost melting
           and latent heat of evaporation of water, respectively. Also in Eq. (3.1), Q com , Q fan , and
           Q air are the energy consumptions by the compressor and supply fan, and the thermal
           energy from the indoor air during defrosting, respectively.
              In this section, the defrosting efficiencies calculated for the three cases were
           43.5%, 50.6%, and 56.7%, respectively. Similar to the previous section, it was
           also demonstrated that allowing melted frost to freely flow down due to gravity would
           lead to more energy consumption during defrosting. There can be two reasons for
           more energy use: (a) evaporating some of the melted frost as mentioned earlier;
           (b) when a defrosting process was prolonged, the fin surface in an up-circuit could
           be dry already while that in a down-circuit was still wet, if not still covered with frost.
           Therefore, thermal energy would be used for just heating the ambient cold air, which
           was highly undesirable. Furthermore, the study results also suggested that the use of
           water-collecting trays was effective in mitigating the negative effects.



           3.3.4 Comparison analysis
           The experimental results by using two-circuit and three-circuit outdoor coils are com-
           paratively analyzed, with their differences summarized in Table 3.7. As seen, after the
           outdoor coil was changed from a two circuit to a three circuit, the defrosting duration
           shorted after the trays used was increased from 16 to 18 s, with the rate decreased from
           15.8% to 7.5%. From the view of indoor thermal comfort, the three-circuit outdoor
           coil improvement is more obvious. Although the differences of the melted frost col-
           lected in two series are similar, at 5.3% for two circuit and 5.0% for three circuit, the
           energy consumed savings are nearly the same, at 10.3% and 10.4%, respectively.
           Finally, after the defrosting efficiency was compared, the improved values for them
           are 10.5% for a two-circuit outdoor coil and 13.2% for a three-circuit outdoor coil,
           respectively. The energy performance also demonstrated that the elimination of the
           melted frost effects is more obvious after the working circuit number increased from
           two to three.
   71   72   73   74   75   76   77   78   79   80   81