Page 292 - Design of Reinforced Masonry Structures
P. 292

5.12                       CHAPTER FIVE

         5.4.3  Reinforcement for Columns
         Reinforcement in masonry columns and pilasters consists of two different forms: longitudi-
         nal (or vertical) and lateral which is provided in the form of ties (as in reinforced concrete
         columns). The longitudinal reinforcing bars participate in carrying their share of load (i.e.,
         the difference between the total load and that carried by masonry alone), but they must be
         laterally supported by ties, for the contribution of the longitudinal reinforcement as load-
         carrying elements cannot be relied upon in the absence of lateral ties. The code specifies
         limitations on clear spacing between bars, and the percentage of cell area for reinforcement,
         which are indirect methods of controlling problems associated with overreinforcing and
         grout consolidation.
           The following code requirements pertain to longitudinal reinforcement and lateral ties:

         5.4.3.1 Longitudinal Reinforcement  The following requirements are specified for longi-
         tudinal (vertical) reinforcement for rectangular or square columns (MSJC-08 Section 1.14):

         1. At least four longitudinal bars, one placed in each corner, must be provided.
         2. Maximum reinforcement area should not exceed 0.04A .
                                                  n
         3. The minimum vertical reinforcement should not be less than 0.0025A .
                                                             n
         4. Longitudinal reinforcement should be uniformly distributed throughout the depth of the
           member.
         5. Bundling longitudinal of bars is not permitted when using the strength design provisions
           of the MSJC Code (Section 3.3.3.6). A maximum of two bars may be bundled if masonry
           is designed under the provisions of allowable stress design (Code Section 1.15.3.4).
           Restriction on bundling of bars is arbitrary and imposed because of lack of research on
           masonry constructed with bundled bars.
         6. The nominal bar diameter should not exceed the following limitations: (MSJC-08
           Section 3.3.3.1):
           (a) No. 9
           (b) One-eighth of the nominal member thickness
           (c)  One-quarter of the least clear dimension of the cell, course or collar joint in which
              the bar is placed.
             Practically speaking, restriction on using large diameter bars for column longitudinal
           reinforcement has been imposed because of grout space limitations; use of smaller bars
           would be usually necessary where splicing would be required. The restriction to using
           No. 9 bar applies when using the strength provisions of the MSJC Code; it is based on
           tests conducted to investigate strength of reinforced masonry for which bars larger than
           No. 9 were not used. Bars up to size No. 11 may be used if allowable stress design pro-

           visions of the code are used. Although the smallest bar size to be used as longitudinal
           steel has not been specified in the Code, No. 3 deformed bars, which are the smallest
           size commercially available deformed bars, should be used as smallest size longitudinal
           reinforcement as a matter of good engineering practice.
         7. Minimum clearance requirements between longitudinal (vertical) bars for both col-
           umns and pilasters are specified by MSJC Section 1.15.3. The minimum clear distance
           between parallel bars is to be not less than 1½ times the bar diameter (1.5d ) nor 1½
                                                                  b
           in. Number of vertical bars arranged along a column face should be checked to satisfy
           this requirement. Table A.17 gives the minimum core width required for placement of
           various numbers of bars along a column face. The minimum clear distance between the
           surface of the bar and any surface of a masonry unit is required to be ¼ in. for fine grout
           and ½ in. for the coarse grout.