Page 490 - Design of Reinforced Masonry Structures
P. 490

7.52                      CHAPTER SEVEN

         Design Category D, E, or F. For inertial forces calculated in accordance with Eq. (7.66),
         the redundancy factor shall equal 1.0. For transfer forces, the redundancy factor shall be the
         same as that used for the structure. For structures having horizontal or vertical structural
         irregularities (of the types discussed in Section 7.8), the requirements indicated in AISC
         7-05 Section 12.3.3.4 shall also apply.

         7.7.3  Design Forces for Chords and Collector Elements

         Shear walls receive their loads from horizontal diaphragms through connections between
         the two elements. A shear wall supporting a diaphragm may be continuous running full
         width of the diaphragm, or it may be discontinuous because of the presence of openings.
         When the shear wall is discontinuous, collector elements (Fig. 7.22) are required to be
         provided such that they are capable of transferring the seismic forces originating in other
         portions of the structure to the element providing the resistance to those forces.

                         Full-length shear wall
                         (collector element not reqd.)
                                                        Discontinuity
                              Partial length shear walls  in shear walls
                              (collector elements reqd. to  (openings)
                              transfer force between
                              diaphragm and shear
                              wall)


                    FIGURE 7.22  Collector elements in discontinuous shear walls.
           In structures assigned to Seismic Design Category C, D, E, or F, collector elements,
         splices, and their connections to resisting elements shall resist the load combinations with
         overstrength specified in ASCE 7-05 Section 12.4.3.2. Example 7.10 illustrates calcula-
         tions for the five story building of Example 7.9.
         Exception: In structures or portions thereof braced entirely by light-frame shear walls,
         collector elements, splices, and connections to resisting elements need only be designed
         to resist forces in accordance with ASCE 0-5 Section 12.10.1.1.

           Example 7.10  Determination of diaphragm forces.
             Calculate diaphragm forces for the five-story building of Example 7.9.

           Solution

             The following information is obtained from Example 7.9.
               TABLE E7.9  Vertical Distribution of Shear (k = 1.0)
                                       k       wh  k  F x = C vx V Story shear
                      h x      w x   w x h x  C vx =   xx
               Level x  (ft)  h x k  (kips)  (kip-ft)  Σ wh  (kips)  (kips)
                                                ii
                 5    60  60   400  24,000  0.280     80.1    80.1
                 4    48  48   450  21,600  0.252     72.1   152.2
                 3    36  36   500  18,000  0.210     60.1   212.3
                 2    24  24   600  14,400  0.168     48.0   260.3
                 1    12  12   650  7,800   0.091     26.0   286.3
                 Σ            2600  85,800  1.001    286.3
   485   486   487   488   489   490   491   492   493   494   495