Page 158 - Electrical Safety of Low Voltage Systems
P. 158

TN Grounding System      141


                                  the same probability to cause ventricular fibrillation. The left-foot-to-
                                  right-foot current path is, therefore, less hazardous and so is the step
                                  voltage, if compared to an equal value of touch voltage.
                                     A European standard 10  takes into account the above considera-
                                  tions, obtaining the permissible values of the step voltage by multi-
                                  plying by the factor 3 the permissible values of the touch voltage, in
                                  correspondence with the same clearing time.



                             FAQs

                                  Q. What is the difference in the status of the neutral wire in TT and TN
                                  systems?
                                  A.  The neutral wire is generally always energized, in some case even at dan-
                                  gerous potentials. In TT systems, the magnitude of the neutral potential de-
                                  pends on faults caused by the utility, therefore, out of customers’ control. For
                                  this reason, the TT neutral wire is conventionally treated as a live conductor,
                                  and always switched off together with the phase conductors.
                                     In TN-S systems, users own and maintain the supply source; therefore,
                                  they can evaluate the risk of the dangerous energization of the neutral wire
                                  and decide how to treat it. In TN-C systems, the neutral is also a protective
                                  conductor (PEN) and, therefore, must not be switched off.
                                  Q. If the fault-loop in TN systems does not comprise the actual earth, why
                                  do we have to ground the source?
                                  A.  TN systems require the system ground. Its purpose is to guarantee the
                                  stability of the operating voltage-to-earth under regular and fault condi-
                                  tions. In addition, the absence of the earth connection of the source would
                                  expose persons to the risk of electric shock, in the conditions depicted in
                                  Fig. 7.3.

                             Endnotes

                                   1. As earlier mentioned, we herein indicate with the underlined symbols the
                                     complex numbers as representative of sinusoids. The same symbols, but with
                                     no underline, or between bars, signify the magnitude of the complex number.
                                     All the network theorems can be applied to sinusoids by means of complex
                                     numbers, as it is illustrated in the final appendices of the book.
                                   2. This sizing is permitted by international standards and codes, as further ex-
                                     amined.
                                   3. In Chap. 12, the effects of high-voltage faults on low-voltage equipment will
                                     be examined.
                                   4. See Chap. 3 for the definition of acceptable risk.
                                   5. Common nonlinear loads may include variable frequency drives and uninter-
                                     ruptible power supplies.
   153   154   155   156   157   158   159   160   161   162   163