Page 153 - Electrical Safety of Low Voltage Systems
P. 153

136   Chapter Seven


                                  FIGURE 7.22 Touch
                                  voltage in TN
                                  systems due to
                                  high-voltage faults.













                                     As a result, the component I S = I F −I G , by not circulating through
                                  the grounding system, lowers both touch and step voltages. This cir-
                                  cumstance might permit less stringent parameters for the design of
                                  the electrode (e.g., the ground grid), by allowing larger earth resis-
                                  tances for it. In the normal practice, though, one can conservatively
                                  consider the larger value I F , instead of I G , as a design parameter for
                                  sizing the electrode.
                                     In high-voltage systems (e.g., industrial facilities), and unlike in
                                                                      7
                                  low-voltage systems, European standards, in establishing the per-
                                  missible limits for touch and step voltages, assume in series to the
                                  body resistance R B , conventionally 1 k , and the person resistance-
                                  to-ground R BG (Fig. 4.15), the resistance of standard footwear of 1 k  8
                                  (Fig. 7.22).
                                     For faults on the secondary side of substations, the following in-
                                  equality is true:


                                                       V   ≤ V   ≤ V                   (7.12)

                                                        T      ST    G

                                  where V G     = R G I .

                                                   F

                                     The touch voltage persists in the system during the time the pro-
                                  tective device takes to clear the fault. However, primary ground faults
                                  may occur outside of the zone of protection of the user’s protective
                                  device. In this case, the duration of the touch voltage depends on the
                                  utility’s clearing time, which is out of the user’s control and cannot be
                                  changed.
                                     Thus, electrical utilities should communicate the fault clearing
                                  time as well as the magnitude of the earth current so that strategies
                                  to minimize the hazards through the proper design of the ground
                                  electrode can be implemented.
                                     Permissible limits of touch voltages V TP compatible with the stan-
                                  dard person in Fig. 7.22 have been elaborated in the aforementioned
                                  European standard as a function of the fault duration (Table 7.3).
   148   149   150   151   152   153   154   155   156   157   158