Page 149 - Electrical Safety of Low Voltage Systems
P. 149

132   Chapter Seven


















                                  FIGURE 7.16 Use of the grounding grid as protective conductor in TN systems.

                                  between the equipment and the grid, as calculated in Eq. (7.11):

                                              V PE1  Z PE2     V PE1
                                       V   =            =               = G V          (7.11)
                                         ST                                   PE1
                                             Z Grid  + Z PE2  (Z Grid /Z PE2 ) + 1
                                     It is clear that the bonding connection to the grid lessens the
                                  prospective touch voltage V PE1 of a factor G depending on the ratio of
                                  Z Grid to Z PE2 , which is generally <1 in magnitude.


                             7.8 TN-C Systems and the PEN Conductor
                                  In TN-C systems, and under specified conditions, the functions of neu-
                                  tral wire and protective wire may be combined in a single conductor,
                                  referred to as PEN conductor. Of course, the PEN conductor, which
                                  besides the neutral current also carries the ground-fault current, must
                                  never be switched off in order to preserve the continuity of the fault-
                                  loop. Basically, by combining two functions in a single wire, a con-
                                  ductor can be avoided, thereby allowing cost reductions, especially
                                  for distribution circuits with large cross-sectional areas. However,


                                  FIGURE 7.17
                                  Equivalent circuit
                                  including the
                                  bonding connection
                                  of ECP to the
                                  grounding grid.
   144   145   146   147   148   149   150   151   152   153   154