Page 146 - Electrical Safety of Low Voltage Systems
P. 146

TN Grounding System      129
























                                  FIGURE 7.12 Transferred potential due to ground faults on final circuits in TN
                                  systems.
                                     As shown in Fig. 7.11, the prospective touch voltage V 1 =
                                  (V ph Z PE1 )/(Z ph + Z PE1 ) is transferred to the healthy stationary equip-
                                  ment (i.e., the electrical motor), whereas the EXCP remains at the earth
                                  potential.
                                     Between the motor and the EXCP, therefore, a potential difference
                                  V 1 arises for a time not exceeding 5 s, even if the load is healthy.
                                  Persons,therefore,areexposedtotheriskofelectricshockeventhough
                                  not in contact with the faulty distribution circuit. This risk, though, is
                                                  4
                                  deemed acceptable by international standards, as the probability of
                                  faults in distribution circuits is assumed low.
                                     Should the fault occur on the stationary equipment, exemplified in
                                  Fig. 7.12 as a motor, the prospective touch voltage V 1 is also transferred
                                  to the healthy mobile equipment (i.e., the drill).
                                     Also in this case, a potential difference V 1 arises between any EXCP
                                  within reach and bonded equipment. The probability of a ground
                                  fault on stationary loads, though, is considerably higher than on a
                                  distribution circuit; therefore, a clearing time of 5 s would pose an
                                  unacceptable hazard to persons. For this reason, European standards
                                  prescribe this clearing time only if the calculated value V 1 does not
                                  exceed 50 V, a value conventionally not dangerous if sustained for no
                                  more than 5 s.

                                  7.6.1 Supplementary Equipotential Bonding
                                  If touch voltages cannot be cleared within the safe time, supple-
                                  mentary equipotential bonding connections (SB) between EXCPs and
                                  ECPs may be employed. Such bonding connections are locally realized
                                  between the enclosures of loads and EXCPs (Fig. 7.13).
   141   142   143   144   145   146   147   148   149   150   151