Page 141 - Electrical Safety of Low Voltage Systems
P. 141

124   Chapter Seven


                                     However, protective devices, RCDs included, must fulfill the fol-
                                  lowing condition applied at the farthest point of the circuit being pro-
                                  tected, where the fault current is at its minimum due to the build-up
                                  of the wires’ impedances:


                                                               V
                                                                ph
                                                       I                                (7.4)
                                                        G  =
                                                                    ≥ I a
                                                               Z Loop
                                  or equivalently, by solving for |Z Loop |,

                                                                 V

                                                                   ph
                                                          Z Loop     ≤                  (7.5)
                                                                  I a
                                  where |I | is the minimum phase-to-protective conductor fault cur-
                                         G
                                  rent and Z Loop is the series of the impedances of the components that
                                  form the fault-loop, specifically the source, the line conductor up to
                                  the farthest point of the fault from the source, and the protective con-
                                  ductor up to the farthest point of the fault. V ph is the system nomi-
                                  nal voltage to ground. I a is the current causing the automatic opera-
                                  tion of the overcurrent protective device within the time specified in
                                  Table 7.1.
                                     IfRCDsareemployed, I a representstheresidualoperatingcurrent,
                                  which provides the disconnection of supply within the time specified
                                  in Table 7.1.
                                     For example, an overcurrent device operating at 230 V, with con-
                                  tinuous rating I n = 16 A, may trip in 0.4 s in correspondence with
                                  I a = 4I n ; therefore, by applying Eq. (7.5), Z Loop ≤ 3.6  . This inequal-
                                  ity is fairly easy to fulfill.
                                     As said, Eq. (7.4), applicable to any point of the circuit being pro-
                                  tected, should, indeed, be verified for ground faults at its end because
                                  that is the point where the smallest amount of fault current is gen-
                                  erated. If the overcurrent device can sense the lowest current in the
                                  circuit and trip within the safe times, the protection against indirect



                                                         Maximum Disconnection
                                   Voltage Range (V)          Times t a (s)
                                   50 < V ph ≤ 120               0.8
                                   120 < V ph ≤ 230              0.4
                                   230 < V ph ≤ 400              0.2
                                   V ph > 400                    0.1

                                  TABLE 7.1  Maximum Disconnection Times as a Function of
                                  the Nominal A.C. Voltage of the TN System
   136   137   138   139   140   141   142   143   144   145   146