Page 138 - Electrical Safety of Low Voltage Systems
P. 138

TN Grounding System      121


                                     It should be noted that Z Th (magnitude of fractions of ohms) could
                                  be neglected, as it is much smaller than the series (R B + R BG ). As a
                                  consequence, there is almost no voltage drop on Z Th and the fault-loop
                                  is virtually an ideal voltage source. The person’s total resistance does
                                  not significantly change the voltage output V Th in case of a contact
                                  and, therefore, V Th equals V ST .
                                     As phase and protective conductor belonging to a same circuit
                                  usually run together, they are characterized by the same length and
                                  type of installation. Therefore, the ratio of their impedances is constant
                                  along their entire route up to the fault location. Ergo, Eq. (7.1) shows
                                  that the magnitude of V ST remains constant regardless of the location
                                  of the fault as long as the ratio of Z ph to Z PE is constant.
                                     If the protective conductor has the same cross section as the phase,
                                  Eq. (7.1) yields: V ST = V ph /2. If the PE has half section of the phase
                                           2
                                  conductor (i.e., Z PE = 2Z ph ), we obtain a larger prospective touch
                                  voltage: V ST = 2V ph /3. Thus, the touch voltage increases where the
                                  PE has a lower section than the phase conductor.

                                  7.2.1 Ground Fault in the Vicinity of the User’s Transformer
                                  Ground faults might occur within an ECP in the vicinity of the user’s
                                  transformer, for example, at the main low-voltage panel (Fig. 7.6).
                                     In this case, the internal impedance Z i of the transformer (Fig. 7.3)
                                  cannot be neglected, as it may be even larger than the conductors’
                                  impedances to the panel because of their short run. By assuming,
                                  therefore, that Z i 	 Z PE and Z i 	 Z ph , we obtain
                                                        V ph Z PE    V ph Z PE
                                               V   =              ∼         = 0         (7.3)
                                                                            ∼
                                                 ST               =
                                                     Z + Z   + Z       Z
                                                      i   PE    ph      i




















                                  FIGURE 7.6 Ground fault in the vicinity of the user’s transformer.
   133   134   135   136   137   138   139   140   141   142   143