Page 135 - Electrical Safety of Low Voltage Systems
P. 135

118   Chapter Seven



















                                  FIGURE 7.1 Ground fault in TN-S systems (three-phase load with no neutral).


                                     In case of a zero-impedance ground fault (i.e., bolted fault), the
                                  current in the fault-loop is limited by the series of the following
                                  impedances: transformer (i.e., Z i ), phase wire (i.e., Z ph ), and protec-
                                  tive conductor (i.e., Z PE ). All as seen at the point of fault. Of course,
                                  the farther the fault occurs from the transformer, the larger is the loop
                                  impedance.
                                     If the fault is not too far from the source, the loop impedance
                                  is low because metal conductors offer high conductivity to currents.
                                  As a result, the ground-fault current is of the same magnitude as a
                                  short-circuit current and can be easily detectedby overcurrent devices.
                                  Consequently,intheseconditions,thepresenceofRCDsinTNsystems
                                  is not strictly necessary for safety.
                                     In only one circumstance can the fault current circulate through
                                  the earth in TN systems. This is the case when the ground fault
                                  occurs toward an extraneous-conductive-parts (EXCPs), which is not
                                  bonded to the grounding system (Fig. 7.2).
                                     In this case, like in TT systems, both the resistance to ground of
                                  the EXCP and R N limit the fault current. The overcurrent device might
                                  not operate in a timely fashion, as this current may be too low. The
                                  risk of dangerous touch potentials, therefore, may arise. A proper
                                  main equipotentialization, that is, a sound connection via the protec-
                                  tive conductor between EXCPs and the system ground, prevents this
                                  hazard and, therefore, is necessary.

                                  7.1.1 Why Earthing the Transformer?
                                  As said, in TN systems the fault-loop does not comprise the actual
                                  earth; however, the user must earth the center of its transformer’s wye.
                                  The purpose of the system ground is to allow the operating voltage-
                                  to-earth to remain stable and to limit overvoltages in fault conditions.
   130   131   132   133   134   135   136   137   138   139   140