Page 140 - Electrical Safety of Low Voltage Systems
P. 140

TN Grounding System      123


                                  FIGURE 7.8
                                  Equivalent fault
                                  circuit and potential
                                  differences in TN
                                  systems.







                                  current through the protective conductor’s impedance Z PE3 . The se-
                                  ries of R N and R EXCP , where R EXCP is the “natural” resistance to earth
                                  of the metalwork entering the building, is much larger than Z PE0 . For
                                  this reason, the series R N + R EXCP can be considered as an open circuit
                                  in Fig. 7.8.
                                     The profile of the prospective touch voltage from the origin of the
                                  electrical system to the faulty equipment is exemplified in Fig. 7.9.
                                     In sum, since V 0 < V 1 < V 2 , we can infer that potential differences
                                  do exist between bonded metal parts during the time the protective
                                  device takes to clear the fault; the magnitude of such potential differ-
                                  ences varies with the location of the ECP as a function of the distance
                                  from the supply.


                             7.4 Protection Against Indirect Contact in TN-S Systems
                                  by Using Overcurrent Devices
                                  In TN systems, overcurrent devices (i.e., circuit breakers or fuses) can
                                  be successfully employed for protection against indirect contact, be-
                                  cause of the large magnitude of the ground currents circulating in
                                  the fault-loop, comparable to that of short-circuit currents. Unlike in
                                  TT systems, then, overcurrent devices in TN systems are facilitated
                                  in detecting, and thereby interrupting, fault currents.


                                  FIGURE 7.9
                                  Prospective touch
                                  voltage profile as a
                                  function of the
                                  distance from the
                                  origin of the
                                  electrical system.
   135   136   137   138   139   140   141   142   143   144   145