Page 147 - Electrical Safety of Low Voltage Systems
P. 147

130   Chapter Seven


                                  FIGURE 7.13
                                  Supplementary
                                  equipotential
                                  bonding (SB) in TN
                                  systems.











                                     The supplementary bond reduces the potential difference between
                                  the EXCP and the faulty ECP to the voltage drop across the protective
                                  conductor employed to realize this equipotential connection, which
                                  must not exceed 50 V.
                                     In addition, the presence of SB decreases the prospective touch
                                  voltage offered by the faulty equipment by “short circuiting” part of
                                  the protective conductor’s impedance (i.e., Z PE1 ).
                                     It is important to note that the equipotentiality in TN systems
                                  is even more crucial than in TT systems because the safety of the
                                  installation depends on it.


                             7.7 Local Earth Connection of ECPs in TN Systems
                                  In TN systems, ECPs are not required to be locally earthed, for exam-
                                  ple, via grounding rods. Nonetheless, the presence of local supple-
                                  mental grounding electrodes may improve the electrical safety of the
                                  installation in areas where the conventional decrease in the driving
                                  voltage (see Sec. 7.4) cannot be applied and the permissible discon-
                                  nection times of Table 7.1 may be excessive. This situation may occur
                                  outside of the equipotential area, for example, around equipment in-
                                  stalled outside of the building, but supplied by a circuit originating
                                  within it. In these zones, the benefits of the main equipotential bond-
                                  ing cannot be enjoyed.
                                     Let us examine Figs. 7.14 and 7.15. The ground fault on the ECP
                                  causes circulation of current through the protective conductor of
                                  impedance Z PE and through the earth, via the series of R N and R G .
                                  The prospective touch voltage V ST is the result of the voltage divider
                                  of V 0 between R N and R G :



                                                         V 0 R G      V 0
                                                  V ST =       =                       (7.10)
                                                       R G + R N  1 + (R N /R G )
   142   143   144   145   146   147   148   149   150   151   152