Page 152 - Electrical Safety of Low Voltage Systems
P. 152

TN Grounding System      135


                                     Safety-related systems (e.g., fire alarm, fire pumps, etc.), that is,
                                  systems whose correct operation is necessary for ensuring or main-
                                  taining safety, may be supplied ahead of the main protective device. If
                                  the corresponding loads are not balanced among the phases, neutral
                                  current will flow. The neutral conductor may result, therefore, ener-
                                  gized, even if the main breaker has been opened. In an emergency
                                  situation, which requires the safety-related systems to be running,
                                  persons (e.g., first responders) may be exposed to the risk of electro-
                                  cution if in contact, directly or indirectly, with the neutral wire, even if
                                  the main breaker is in the open position. In this case, the simultaneous
                                  switching off of neutral and line conductors is a safety requirement.


                             7.10 The Touch Voltage in TN Systems
                                  As already anticipated in Chap. 4, in electrical systems exceeding 1 kV,
                                  defined as high-voltage systems, international standards convention-
                                  ally define the touch voltage as the potential difference between faulty
                                  equipment touched with one hand and the two feet of the person. 6
                                  Ground faults occurring on the primary side of substations cause cir-
                                  culation of currents through the earth and therefore also step poten-
                                  tials. In reality, part of the fault current I F may be prevented from
                                  circulating through the ground, with benefits for the safety. Upon per-
                                  mission of the local utility, in fact, the metallic sheaths of their incom-
                                  ing power cables, or the overhead ground wires of their transmission
                                  lines, may be used to drain off part of the fault current provided that
                                  the sheaths are adequately sized to withstand such current (Fig. 7.21).



























                                  FIGURE 7.21 Earth current due to primary side faults.
   147   148   149   150   151   152   153   154   155   156   157