Page 162 - Electrical Safety of Low Voltage Systems
P. 162

Protective Multiple Earthing (TN-C-S Grounding System)       145
























                                  FIGURE 8.3 Fault-loop in PME systems for single-phase loads.

                                     Unlike in TT systems, the PME customer need not install its own
                                  grounding system. In fault conditions, the earth will be partially in-
                                  volved as a return path to the source because of the connection of the
                                        1
                                  EXCPs to the main grounding bus (Fig. 8.3). As already substantiated,
                                  this bond is essential to guarantee equipontiality between simultane-
                                  ously accessible metal parts.
                                     Moreover, in the absence of ground faults, the above earthing ar-
                                  rangement may cause part of the neutral current to return to the source
                                  through the earth. In PME systems, therefore, the ground becomes a
                                  path to the utility transformer and the circulation of “stray currents”
                                  is unavoidable.
                                     In PME systems, ground-fault currents arising at the user’s loca-
                                  tion have large magnitude, as their return path is a conductor, that is,
                                  the PE and the PEN to which the earth is in parallel. Therefore, the
                                  total impedance of the fault-loop |Z Loop | may be low enough to allow
                                  users to use overcurrent devices as protection against indirect contact.
                                  A large ground-fault current, in fact, can easily fulfill Eq. (7.4). Hence,
                                  the presence of RCDs in PME systems is not a mandatory safety re-
                                  quirement, as is in TT systems.
                                     The combined neutral and protective conductors (PEN) may exist
                                  throughout the utility low-voltage distribution system, as this allows
                                  some savings in the length of cables to be employed (i.e., four-wire
                                  distribution system), whereas, within the user’s installation, neutral
                                  and protective conductors may be separate (i.e., five-wire distribution
                                  system).Insomecountries(e.g.,Norway,U.S.A.),theuseofaPENcon-
                                  ductor downstream of the user’s main distribution panel is forbidden.
                                     In PME systems, the bonding connection is of utmost importance,
                                  at the service entrance of the dwelling unit, between the PEN and
   157   158   159   160   161   162   163   164   165   166   167