Page 164 - Electrical Safety of Low Voltage Systems
P. 164

Protective Multiple Earthing (TN-C-S Grounding System)       147



















                                  FIGURE 8.4 Ground fault on low-voltage distribution system.


                                  units by means of their ground electrodes (e.g., cold water pipe). R E is
                                  the minimum earth resistance of EXCPs not connected to an equipo-
                                  tential system, through which a fault may occur.
                                     The earth current, by circulating through R N and R E energizes the
                                  PEN conductor and, therefore, the user’s ECPs. The contact resistance
                                  with earth also limits this ground current and in some cases can be
                                  very high (e.g., line in contact with snow or sand). The distributor’s
                                  overcurrent devices, therefore, may not be able to clear the fault within
                                  the maximum permissible times of Table 7.1, exposing persons to the
                                  risk of electric shock.
                                     To identify safe values for the PEN potential and the maximum
                                  earth resistance R N , let us examine Fig. 8.5 and Eq. (8.1):


                                                      R N                 R N
                                     V N = V ph ×               ∼              ≤ 50     (8.1)
                                                                = V ph ×
                                               R E + R N + Z i + Z ph   R E + R N

                                  In Eq. (8.1), we can ignore both the phase conductor impedance Z ph
                                  and the internal impedance of the source Z i because they are generally
                                  negligible with respect to R N and R E . As a safety criterion, we can
                                  assume as “safe” the PEN conductor if its potential V N does not exceed
                                  the safety limit of 50 V.



                                  FIGURE 8.5
                                  Fault-loop for a
                                  ground fault on the
                                  low-voltage PME
                                  distribution system.
   159   160   161   162   163   164   165   166   167   168   169