Page 166 - Electrical Safety of Low Voltage Systems
P. 166

Protective Multiple Earthing (TN-C-S Grounding System)       149





















                                  FIGURE 8.7 Distinct grounds at the utility transformer.

                                     This strategy, although effective for the customers, is not free of
                                  risk for the utility’s operators engaged in maintenance activity within
                                  the substation. The PEN conductor, in fact, becomes an EXCP, liable
                                  to introduce a “zero” potential or a fault potential into the premises.
                                  With this arrangement, workers must take precautions and treat the
                                  PEN as a “live” conductor.

                                  8.2.3 Faults Phase-to-PEN in Low-Voltage PME Networks
                                  Another cause of energization of the PEN conductor may be the ac-
                                  cidental contact with the phase conductor in low-voltage distribution
                                  networks (Fig. 8.8).
                                     The resulting short circuit causes a circulation of current back to
                                  the source through the PEN conductor. We assume to neglect the fault
                                  current derived by the EXCPs at the user’s location, connected for





















                                  FIGURE 8.8 Short circuit phase-to-PEN in PME.
   161   162   163   164   165   166   167   168   169   170   171