Page 165 - Electrical Safety of Low Voltage Systems
P. 165

148   Chapter Eight


                                     From Eq. (8.1) we can derive the condition R N must comply with
                                  to keep the PEN potential rise below 50 V:

                                                         R N     50
                                                            ≤                           (8.2)
                                                         R E  V ph − 50

                                  In some countries (e.g., Germany), fulfilling Eq. (8.2) is a compulsory
                                  requirement for the supply network operators.


                                  8.2.2 Ground Fault on the Medium-Voltage Utility
                                         Distribution System
                                  The enclosure of the utility transformer, being an ECP, needs to be
                                  earthed and therefore may be connected to the system ground R N .
                                  Low- and medium-voltage systems, then, share the same earth termi-
                                  nal where the PEN conductor originates.
                                     At the occurrence of a ground fault at the transformer primary,
                                  the fault current by circulating through the earth and reclosing
                                  toward the upstream source of the supply network energizes the sys-
                                  tem ground. R N reaches the potential V N and so does the PEN con-
                                  ductor (Fig. 8.6).
                                     Consequently,personsincontactwithlow-voltageECPs,remotely
                                  supplied by the “live” PEN, are exposed to the whole earth potential
                                  V N during the utility fault-clearing time.
                                     In PME, utilities, in order to ensure that the neutral potential due
                                  to primary faults is not dangerous, must accordingly lower the neutral
                                  resistance R N . When it is impossible to decrease R N , the distributor
                                  must alternatively separate the service PEN conductor from the trans-
                                  former enclosure’s earth by creating two distinct grounds (Fig. 8.7).






















                                  FIGURE 8.6 Ground fault at the transformer primary.
   160   161   162   163   164   165   166   167   168   169   170