Page 167 - Electrical Safety of Low Voltage Systems
P. 167

150   Chapter Eight


                                  FIGURE 8.9
                                  Equivalent fault-loop
                                  for a short circuit
                                  phase-to-PEN
                                  in PME.











                                  equipotential reasons to the PEN. Such current, in fact, is greatly lim-
                                  ited by the EXCPs’ resistance-to-ground, which is much larger than
                                  the impedance of the PEN conductor. The equivalent fault-loop circuit
                                  is shown in Fig. 8.9.
                                     By assuming both the internal resistance of the source to be neg-
                                  ligible and the cross-sectional area of the PEN as half of the phase
                                  conductor (common situation), the user’s ECPs will reach the follow-
                                  ing prospective touch voltage:

                                                  Z PEN             2Z ph     2
                                    V ST  = V ph  ×      = V ph  ×         =   × V ph   (8.3)
                                               Z    + Z          2Z   + Z     3
                                                 PEN   ph           ph   ph
                                  Users are exposed to this voltage for the time the distributor’s protec-
                                  tive device takes to clear the fault.

                             8.3 Interruption of the PEN Conductor in PME
                                  As already substantiated in Sec. 7.8 for TN systems, the accidental in-
                                  terruption of the PEN conductor causes all the ECPs supplied down-
                                  stream of the interruption to be energized at the line-to-line potential,
                                  even if healthy. PME have a much larger geographical extension than
                                  TN systems and therefore the risk of the interruption of the PEN con-
                                  ductor and of the energization of the ECPs of more than one customer
                                  is higher. Hence, the installation of the PEN conductor should be in
                                  such a way as to minimize the probability of its break.
                                     ThelossofthePENconductoralsotriggersovervoltages.Letusex-
                                  amine Fig. 8.10, where two users are supplied by two different phases
                                  and the same PEN.
                                     The absence of the PEN as a return path causes a voltage divider
                                  between the two users’ single-phase loads, which are now supplied
                                  by the line-to-line voltage. This may cause the supply to each load
                                  to exceed the nominal value, with great risk of overheating of the
                                  equipment and therefore of initiating fire.
   162   163   164   165   166   167   168   169   170   171   172