Page 163 - Electrical Safety of Low Voltage Systems
P. 163

146   Chapter Eight


                                  the PE. It is, therefore essential to periodically inspect and maintain
                                  such connection. Upon loss of this bond, the building would become
                                  a TT system, wherein in the absence of RCDs, which are not strictly
                                  necessary in PME, users are exposed to electric shock hazards.

                                  8.1.1 Fault-Loop Impedance in PME Systems
                                  As said, low fault-loop impedances guarantee the safe operation of the
                                  user’s overcurrent protective device with respect to the permissible
                                  times of Table 7.1.
                                     In TN systems, Z Loop exclusively depends on parameters known
                                  to the user, such as the impedances of circuits and transformers. In
                                  PME, instead, the fault-loop impedance includes the impedance Z e of
                                  the utility low-voltage distribution system, which is usually unknown
                                  to the customer. Z e , which increases with the distance of the fault’s
                                  location from the supply source, may also change in time without the
                                  user knowing it because of modifications in the utility distribution
                                  system. If the total fault-loop impedance Z Loop = Z e + Z user is exces-
                                  sive, the ground fault current might be so low that Eq. (7.4) cannot be
                                  fulfilled, and there would be no effective protection of persons against
                                  indirect contact.
                                     The installation of RCDs in dwelling houses, even in PME systems,
                                  although redundant in the case of low value of Z Loop , can, indeed,
                                  guarantee safety when Z Loop is too high.

                             8.2 Energization of the PEN Conductor in PME Systems
                                  PME systems imply a considerable responsibility of the local utility,
                                  since, together with the electric energy, the distributor provides the
                                  users with an earth connection, which must ensure public safety.
                                     In fault conditions, the utility PEN, although multiple grounded,
                                  may assume a voltage, with respect to the earth, as is substantiated
                                  later on. Such neutral-to-ground voltage can be transferred as a shock
                                  potential to the users’ ECPs and EXCPs. If utilities cannot “certify”
                                  the neutral potential as harmless to persons, a TT system should be
                                  employed, instead.

                                  8.2.1 Ground Fault on the Low-Voltage Utility
                                         Distribution System
                                  The PEN conductor may become live due to a ground fault occurring
                                  along its distribution system, for example, as a result of the fall to earth
                                  of overhead cables (Fig. 8.4) or of a contact of the line with an EXCP
                                  not connected to a protective conductor.
                                     R N represents the ground resistance of the utility’s earth electrode
                                  system: the neutral conductor is earthed not only at intervals along its
                                  run (e.g., at the transmission poles) but also at the customers’ dwelling
   158   159   160   161   162   163   164   165   166   167   168