Page 315 - Electromechanical Devices and Components Illustrated Sourcebook
P. 315

Chapter 16  Electrostatics 277

                                                                   Corona
                                 5
               Insulation Tester   0 1  2  20 30 3  4 40 50 60 70 6  7  8  9 10                      Rounded Tip
                               10  80  90 100
                  (Megger)    0  Mega Ohms
                                                               Sharp Tip
                                                                     High                          Low
                                                                   Leakage                        Leakage







                                 Insulated
                                Drive Shaft                                  High             High
         Component to Be Floated                                            Voltage          Voltage
            at High Voltage
                                                               Figure 16-8 Corona Discharge
                                                Control Panel
         Figure 16-7 Verifying High-Voltage Isolation with a Megger




        any high voltage that may leak to the panel will be immedi-  I turned on the lights, de-energized the circuit and carefully
        ately grounded and, therefore, the operator will be protected.  applied high-voltage silicone rubber to all of the soldered and
           Testing the stand-off voltage capability of a design can be  bolted joints. The next morning I re-energized the circuit and
        accomplished by using an insulation tester, or megger, as  it produced its full 10,000-volt output. The solder and bolted
        shown in Figure 16-7. These tests should be carried out only  joints were leaking 80% of the power supply’s voltage to air!
        while the equipment is de-energized. Additionally, any high-  Figure 16-9 shows an example of poor high-voltage solder
        voltage isolation system should undergo regularly scheduled  joint and the use of high-voltage silicon rubber to suppress
        inspections.                                          leakage.
                                                                 The slow build up of dirt can also produce high-voltage
                                                              leaks. This is particularly problematic with equipment that is
                                                              forced to operate in dirty and dusty environments. High-
        Corona Discharge and High-Voltage                     performance cabinet filtration will help mitigate the effects of
                                                              dirt built-up. Figure 16-10 shows how an exposed stand off
        Leaks                                                 insulator can be protected from dirt build-up by using a pro-
                                                              tective boot. In this case, the leakage would be from the
        Corona discharge happens when a conductor is forced to
                                                              terminals to the grounded case. If the case is floating, the
        carry more electrons than it can accommodate. In these
                                                              leakage would be between the terminals forming a bypass of
        instances the electrons jump into the air where they flow to
                                                              the component.
        any neutralizing charge that they may find. Near the conduc-
                                                                 Carbon paths, as shown in Figure 16-11, are an insidious
        tor the electrons have sufficient energies to ionize the air and
                                                              problem that will build over time.  There are two principal
        force it to glow, or in other terms produce a corona.
                                                              ways that carbon paths can develop. The first being during
           The most common reason for electron concentration is
        sharp points on the conductor. The electrons concentrate at
        the diminishing point and eventually are forced off the con-
        ductor. As an example, the sharp tip of the conductor on the
        left hand side of Figure 16-8 will have a great deal of leakage
        at high voltage and will, most likely, glow with a low purple                              Sharp Solder
        light. On the other hand, the conductor on the right, with its                             Points
        rounded tip, will have very little leakage and will stand off                               Cut Wire Ends
        much higher voltages.
           Solder joints are always a trouble spot in high-voltage cir-                           Sharp Component
                                                                                                  Edges
        cuits. In one instance I designed and constructed a 10,000-
                                                                                              Insufficient Spacing
        volt DC power supply for an industrial flash unit. When I                              From Ground
        energized the circuit, it was outputting only 2000 volts. As I
        probed the circuit I noticed that the voltage got progressively                          High-Voltage Silicon
        lower as I worked through from the transformer secondary to                              Rubber to Suppress
                                                                                                     Leakage
        the output of the supply. This was puzzling. Without any other
        ideas, I turned off the lights and noticed that the entire circuit
        was glowing brightly from numerous corona discharge sites.  Figure 16-9 Suppressing Corona Discharge
   310   311   312   313   314   315   316   317   318   319   320