Page 216 - Estimators Piping Man Hour Manual
P. 216

Section Six—HANGERS AND SUPPORTS          199

                      HANGERS        AND    SUPPORTS

     Fabrication:  Labor  only  for  fabrication  of other  than standard  manufactured hangers and sup-
        ports can be performed  at 0.07 man hours per pound.

     Field  Erection:
                                                         Man  Hours  Per  Hanger 41
       Type  of  Hanger    Hanger  Suspended  From        Hanger  Fastened To
                                                           Concrete     Exist-
                                                              or          ing
                                                      Steel Masonry Wood Pipe
        PATENT     Welded Clip Angle                  1.50    --     ..   ..
                   Clip  Angle  —  Ramset             1.00                --
                                                              —      —
                    Female Stud or  Male  _
                   Stud 6 Coupling  ~~ ™ mset          .60    .60
     Clevis  Hanger
     Band  Hanger   Female Stud or Male _  Nelson stud Welder  .60        —
     Ring  Hanger  Stud  & Coupling                                  —
     Expansion  Hanger
                   Beam  Clamp or  Corn  Clamp        1.30
                   Cinch Anchor                              2.00
                                                       —             —    —
                   Bolt  or  Strap                                  1.60
                                                       —      —           —
                   Band  and  Rod                                        1.00
                                                       —      —      —
        PATENT     Welded Clip  Angles                2.00
                                                              —      —    —
                   Clip  Angle  —  Ramset             1.50    ..
                                                                     —    —
                    Female Stud or  Male  r» Q,woo»
                   Stud & Coupling   ""  RamS6t       1.20
     Trapeze  Hanger
     (!' - 4'  Bar)  Female Stud or Male _  Nelgon g  d  w  1.20     »_   _„
                   Stud  fi  Coupling                         —
                   Beam Clamp or  Corn Clamp          2.00    ._
                                                                     —    —
                   Cinch Anchor                              4.00       ;.  —
                                                       —             —
     *The  patent  hanger allowances are for  supporting pipe  through 4" size.

     Fabricated  Hangers (Angles, Channels, Etc. ):  0. 08  man  hours  per  pound with a minimum time
        of  1 man hour regardless of weight.
     The following factors  should  be applied for  sizes over  4":
        6"  —-  1.20 man hours
        8"  —  1. 50 man  hours
        10"  —  1.80 man hours
        12"  —  2. 20 man  hours