WATER TREATMENT AND PURIFICATION

                      4.42                       CHAPTER FOUR

                      TABLE 4.10  ASTM Reagent-Grade Water Specifications

                                                               Type I        Type II
                      Resistivity (Megohm-cm compensated to 25 °C)   18.0     1.0
                      TOC (ppb)                                100            50
                      Sodium (ppb)                              1              5
                      Chlorides (ppb)                           1              5
                      Silica (ppb)                              3              3





                      TABLE 4.11  NCCLS/CAP Reagent Water Specifications

                                                       Type I                  Type II
                      Resistivity (Megohm-cm @ 25 °C)   10                       1.0
                      Silicate (mg/L SiO 2 )           0.05                      0.1
                      TOC (ppb)                    Activated carbon (not required by    Not specified
                                                   CAP) or distillation or RO
                      Particulates                 0.22 micron filter         Not specified
                      Bacteria (cfu/mL)                 10                      1,000
                      Additional purification may be required for selected clinical laboratory procedures such as:
                       1. Preparation of water with minimal pyrogen levels for cell culture

                       2.  Preparation of bacteria-free water for direct fluorescent detection of bacteria as in Legionella direct fluorescent
                       antibody testing or direct fluorescent stains of mycobacteria
                       3. Preparation of water with minimal organic content for HPLC


                          TABLE 4.12  AAMI/ANSI Water Quality Standards

                          Contaminant                 Suggested maximum level, mg/L
                          Calcium                            2 (0.1 mEq/L)
                          Magnesium                          4 (0.3 mEq/L)
                          Sodium                             70 (3 mEq/L)
                          Potassium                          8 (0.2 mEq/L)
                          Fluoride                           0.2
                          Chlorine                           0.5
                          Chloramines                        0.1
                          Nitrate (N)                        2
                          Sulfate                            100
                          Copper, barium, zinc               0.1 each
                          Arsenic, lead, silver              0.005 each
                          Chromium                           0.014
                          Cadmium                            0.001
                          Selenium                           0.09
                          Aluminum                           0.01
                          Mercury                            0.0002
                          Bacteria                           200 (cfu/mL)
                          Source:  Association for the Advancement of Medical Instrumentation (AAMI)
                          “Hemodialysis Systems Standard,” March 1990. Adopted by American National
                          Standards Institute (ANSI), 1992.



                   Downloaded from Digital Engineering Library @ McGraw-Hill (www.accessengineeringlibrary.com)
                              Copyright © 2009 The McGraw-Hill Companies. All rights reserved.
                                Any use is subject to the Terms of Use as given at the website.
   201   202   203   204   205   206   207   208   209   210   211