Page 374 - Failure Analysis Case Studies II
P. 374

359






















                                                Fig. 3. Corrosion damage of cables.



                     reduction of area and, particularly, the number of bend/rebends; also, indirectly, the brittleness of
                     the material. The  fractured  surfaces were analysed  in  detail  by  fractographic  examination. The
                     average values of the parameters obtained from the mechanical tests are shown in Table 1,
                       From the results given in Table 1 it can be concluded that only the uncorroded wire (Corr. d. = 0)
                     satisfied the requirements of the original tender. R,,,z  and R, are still within the permitted  limits.
                     The elongation is greater than the minimum prescribed value of 4%, reduction of area exceeds the
                     minimum prescribed value of 25%,  and the number of bends/rebends is near the minimum required
                     limit, i.e. 4. However, in the case of all the other test specimens the mechanical properties worsen
                     as the degree of corrosion increases, and there is an important increase in  the brittleness  of  the
                     material.
                       The  (SEM)  fractographic  analyses  of  the  fractured  surfaces  of  the  test  specimens, after  the
                     mechanical testing, agree well with the results  shown in Table  1. The material defined by  Corr.
                     d. = 0 is tough (Fig. 4). In the middle a so-called fibrous zone can be seen, where the crack is only
                     progressing slowly. This means  that for the crack to progress during the tension test in a stable
                     manner,  a relatively large amount of energy is needed. In the shear-lip zone  (the ring area  sur-
                     rounding the fibrous zone) a change in the rate of progress of the crack can be observed. In this
                     area  its  spreading  is unstable and quicker.  In the fibrous zone  the fracture  surface with  typical
                     relatively large dimples (Fig. 5) appears tough. A tough fracture can also be observed in the shear
                     zone, but, as the material  in  the tension test slips at an angle of 45”, characteristic shears occur
                     which make the characteristic dimples more or less invisible.
                       It is quite clear that stress corrosion and hydrogen embrittlement reduce the size of the fibrous
                     and shear-lip zones (Figs 6 and 7), and the proportions in both of brittle locations increases. It is a
                     fact that the nucleation and propagation of microcracks, their coalescence into larger cracks together



                                       Table 1. The mechanical characteristics of typical test specimens
                             Actual                                                 No. of
                     Corr.   cross-section   4.0   R,    Elongation   Reduction   bendslrebends
                                           2
                      d.      (mm’)     (Nimm’)   (mm’)   Am (%)    of area (%)   over 45 mm dia.
                       0      38.5       1546     1793      6.3        40            3.5
                       1      38.0       1418     1616      5.1        36            3.0
                       2      35.0       1221     1408      5.6       ca. 20         2.5
                       3      35.0       1325     1546      2.9       ca. 20         2.0
                       4      25.0       -        857       2.0        0             0.5
                       5      22.0        -       878       2.0        0       Breaks at an angle of 25
                     Note: RN2 and R,  have been calculated taking into account a nominal diameter of 7 mm, 1.e. a cross-section of 38.5 mm’.
   369   370   371   372   373   374   375   376   377   378   379