Page 255 - HVAC Pump Handbook
P. 255

Rishel_09.qxd  20/4/06  6:34 PM  Page 252




                                       Configuring an HVAC Water System

                    252   The HVAC World

                    TABLE 9.1 System Head Curve
                    Coordinates

                     System flow, gal/min  System head, ft
                           0100              021.0
                           0200              023.8
                           0300              028.1
                           0400              034.0
                           0500              041.4
                           0600              050.3
                           0700              060.6
                           0800              072.4
                           0900              085.5
                           1000              100.0


                    9.3.2 System head areas
                    The preceding example and data describe systems with uniform flow in
                    all heating or cooling coils. Obviously, this does not exist in most actual
                    buildings, since some coils will be loaded while others will not have any
                    load on them. If the building has windows, as the sun moves around
                    the building during the day, the loads on the various coils will change
                    even with constant outdoor temperature and internal load. This is also
                    demonstrated by the term diversity, which was defined in Chap. 1.
                      Recognizing that systems are not loaded uniformly and that diver-
                    sity does exist, we must evaluate chilled and hot water systems to
                    determine how to compute and display graphically the actual head on
                    them. Figure 9.3a describes a typical building with 10 air-handling
                    units on different floors; this will be our model building to illustrate a
                    typical system head area. The uniform system head curve for this
                    building is shown in Fig. 9.3b. Assume that a 40 percent uniform load
                    occurs on each of the 10 air-handling units; this is detailed graphi-
                    cally in Fig. 9.4a. Now, let the 40 percent load shift so that only the
                    four bottom coils are fully loaded and the top six coils have no load on
                    them (see Fig. 9.4b). Since these four coils are nearer to the pumps
                    than all 10 coils, the system friction will be less than that for all 10
                    coils uniformly loaded at 40 percent each, namely 2 ft of friction, next,
                    transfer all the 40 percent load to the upper four coils (see Fig. 9.4c).
                    Now the load is farther than all the 10 coils uniformly loaded, and the
                    system friction head will be greater than that for the uniformly loaded
                    condition, in this case, the system friction will be 72 ft. This procedure
                    can be done for various loads on the building, from 10 to 90 percent
                    load. The result of these moves of the load on the building is shown in
                    Fig. 9.5a; this is a system head area, and it exists for almost any build-
                    ing with more than one heating or cooling coil. This is one of the most
                    important figures in this entire book, since it makes the designer




                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   250   251   252   253   254   255   256   257   258   259   260