Page 218 - Handbook of Electrical Engineering
P. 218

202    HANDBOOK OF ELECTRICAL ENGINEERING

                      Table 9.14. Land based installations. 600/1000V. Cu/PVC/PVC/SWA/PVC 3 and 4 cores

                     Nominal       Air    Ducts    Direct                 Notes
                     conductor                     buried
                            2
                     area (mm )
                         10
                         16        87       78       97
                         25       116      103      126
                         35       142      123      150
                                                                                     ◦
                         50       175      146      178      Thermal resistivity of soil is 1.2 Cm/W
                         70       218      181      220
                                                                                   ◦
                         95       268      218      264      Ambient air temperature is 30 C
                        120       310      247      299      Depth of laying cables is 0.5 m
                        150       355      279      335
                                                                                       ◦
                        185       407      314      377      Standard ground temperature is 15 C
                                                                                        ◦
                        240       480      363      435      Conductor surface temperature is 70 C
                        300       547      407      486
                        400       627      466      546
                                         ◦
                        Ambient air temperature C  25  30  35    40    45  50   55   60
                        Rating factor for cables laid in air  1.02  1.0  0.94  0.87  0.79  0.71  0.61  0.50


                      Table 9.15. Land based installations. 600/1000 V. Cu/XLPE/PVC/AWA/PVC single core
              Nominal     Air      Air     Ducts          Direct buried               Notes
              conductor  trefoil    3      trefoil
                     2
              area (mm )        horizontally      trefoil   3           3
                                  spaced                horizontally  horizontally
                                                          touching    spaced
                  50      231      296      231    231      231        242     Thermal resistivity of
                                                                                        ◦
                  70      295      373      278    284      283        295       soil is 1.2 Cm/W
                  95      362      452      327    340      337        350     Ambient air temperature
                                                                                    ◦
                 120      420      519      366    386      381        395       is 25 C
                 150      483      577      396    431      424        434     Depth of laying
                 185      555      649      437    485      474        482       cables is 0.5 m
                 240      654      745      489    558      542        545     Standard ground
                                                                                              ◦
                 300      745      825      534    623      601        597       temperature is 15 C
                 400      851      887      567    691      657        637     Conductor surface
                                                                                              ◦
                                                                                 temperature is 90 C
                               ◦
              Ambient air temperature C         25    30    35   40    45    50   55    60
              Rating factor K air for cables laid in air  1.0  0.96  0.92  0.88  0.84  0.79  0.73  0.68
                            ◦
              Ground temperature C              10    15    20   25    30    35   40
              Rating factor K grd for Cables laid in the ground  1.03  1.0  0.97  0.93  0.89  0.86  0.82
              9.4.2.1 Derating factor due to ambient air temperature


              Manufacturers quote current ratings of their cables laid in air at a particular ambient temperature
                    ◦
                                   ◦
                          ◦
              e.g., 25 C, 30 C and 45 C. They also provide tables of derating factors (K air ) based on the chosen
              ambient temperature, see the above tables, and Chapter 8 of Reference 4.