CABLES, WIRES AND CABLE INSTALLATION PRACTICES     203

           Table 9.16. Land based Installations. 600/1000 V. Cu/XLPE/PVC/AWA/PVC single core Cu/XLPE/PVC/
           SWA/PVC 3 and 4 core
           Nominal conductor      Single core            3and4            Approximate armouring
                     2
              area (mm )           in trefoil             cores                 resistance
                                                                                             ◦
                                                                                ◦
                            Resistance  Reactance at  Resistance  Reactance  AWA at 80 C  SWA at 80 C
                                 ◦
                                                        ◦
                             at 90 C     50 Hz      at 90 C   at 50 Hz   (ohm/km)     (ohm/km)
                             (ohm/km)   (ohm/km)   (ohm/km)  (ohm/km)     1-core       3/4 core
                  1.5                              15.4        0.103                   11.40
                  2.5                               9.45       0.101                    9.48
                  4                                 5.88       0.0929                   5.52
                  6                                 3.93       0.0885                   4.92
                 10                                 2.33       0.0835                   4.08
                 16                                 1.47       0.0815                   2.64
                 25                                 0.927      0.0818                   2.52
                 35                                 0.668      0.0771                   2.28
                 50           0.494      0.104      0.494      0.0765      1.018        1.56
                 70           0.342      0.101      0.342      0.0754      0.919        1.44
                 95           0.246      0.0969     0.247      0.0727      0.795        1.176
                120           0.196      0.0920     0.197      0.0723      0.559        0.852
                150           0.160      0.0945     0.160      0.0728      0.509        0.780
                185           0.128      0.0932     0.128      0.0730      0.460        0.708
                240           0.0985     0.0902     0.0989     0.0722      0.410        0.624
                300           0.0799     0.0883     0.0802     0.0717      0.385        0.564
                400           0.0639     0.0886     0.0656     0.0715      0.286        0.408

                  Table 9.17. Land based installations. 600/1000 V. Cu/XLPE/PVC/SWA/PVC 3 and 4 cores
           Nominal conductor    Air     Ducts     Direct buried               Notes
                     2
              area (mm )
                1.5             26        26           32
                2.5             35        34           42
                4               47        45           55
                6               59        56           69
               10               82        75           92
                                                                                         ◦
               16               107       96          119         Thermal resistivity of soil 1.2 Cm/W
               25               140      124          152
                                                                                    ◦
               35               172      149          182         Ambient air temp. is 25 C
               50               209      177          217         Depth of laying cables is 0.5 m
               70               263      218          266
                                                                                        ◦
               95               324      263          319         Standard ground temp. is 15 C
                                                                                         ◦
              120               376      300          363         Conductor surface temp. is 90 C
              150               430      338          406
              185               495      382          458
              240               584      442          529
              300               666      496          592
              400               766      570          667
                            ◦
           Ambient air temperature C         25    30   35    40    45   50    55   60
           Rating factor K air for cables laid in air  1.0  0.96  0.92  0.88  0.84  0.79  0.73  0.68
                         ◦
           Ground temperature C              10    15   20    25    30   35    40
           Rating factor K grd for cables laid in the ground  1.03  1.0  0.97  0.93  0.89  0.86  0.82